66
EVENT
STARTS WHEN...
ENDS WHEN...
0906
(0487)
Warning
wireless devices
...the VectorRX Receiver does not respond
to the Control Panel
...The VectorRX Receiver responds to the
Control Panel
0907
(0488)
False key
...a false Key/Card is used at a Reader
...ALL false Keys/Cards have been with-
drawn from the Readers
0908
(0489)
Warning fuse +F
...fuse
37
blows
...fuse
37
is replaced
0909 Warning fuse
+F1
...fuse
36
blows
...fuse
36
is replaced
0910
(0490)
Warning fuse
+B1
...fuse
46
blows
...fuse
46
is replaced
0911 Warning fuse
+B2
...fuse
45
blows
...fuse
45
is replaced
0912 Warning fuse
+B3
...fuse
44
blows
...fuse
44
is replaced
0913 Warning fuse
+B4
...fuse
43
blows
...fuse
43
is replaced
0914 Warning fuse
+B5
...fuse
42
blows
...fuse
42
is replaced
0915
(0491)
Warning fuse
BPI1
...fuse
35
blows
...fuse
35
is replaced
0916
(0492)
Warning fuse
BPI2
...fuse
34
blows
...fuse
34
is replaced
0917
(0493)
Warning fuse
KEYBUS
...fuse
29
blows
...fuse
29
is replaced
0918
(0494)
Warning mains
failure
...Mains power has been off for the pro-
grammed Timeout (refer to "Options")
...Mains power is restored
0919
(0495)
Warning low
battery
...Battery voltage drops below 11.4V
...Battery voltage is restored to 12.3V
0920
(0496)
Warning power
trouble
...a Battery fails the Dynamic Test (refer to
"Connecting the Power supply" under
"INSTALLING THE KYO300"), or fuse
60
blows
...Battery meets the Dynamic Test require-
ments, or fuse
60
is replaced
0921
(0497)
Warning mains
failure on Power
station
...the programmed Timeout expires (refer to
"Power stations" under “Configuration”). The
Timeout will start when the Control panel de-
tects failure of the Mains supply — to one of
the BPI Bus Power Supply Stations.
...Mains power is restored to ALL the BPI
Bus Power Supply Stations
0922
(0498)
Warning low
battery on
Power station
...the Battery Voltage of a BPI Power Sup-
ply Station drops below 11.4V
...the Battery voltage of ALL BPI Power
Supply Stations restores to 12.3V
0923
(0499)
Warning power
trouble on
Power station
...the Battery of a BPI Bus Power Supply
Station fails the Dynamic test, and there-
fore, is unable to feed and ensure proper
functioning of the peripherals; or the Power
Supply Station polarity inversion fuse blows
...the Batteries of ALL the BPI Bus Power
Supply Stations pass the Dynamic test, or
ALL the Power Supply Station polarity in-
version fuses are replaced
0924
(0500)
Battery not
connected on
Power station
...the voltage of a Power station battery
drops below 10.2 V
the voltage of ALL the Power station batter-
ies rises above 10.2V
0925
(0501)
Battery charger
trouble on
Power station
...the output voltage of a Power station
power supply module is 0.5 V above or be-
low the preset value
14
...the output voltage of ALL the Power sta-
tion power supply modules is 0.5 V above
or below the preset value
0926
(0502)
Switching not
connected on
Power station
...the output voltage of a Power station
power supply module is 0.5 V above the
preset value
...the output voltage of ALL the Power sta-
tion power supply modules is 0.5 V below or
equal to the preset value
0927
(0503)
Short circuit
output 1/2/3 on
Power station
...the current draw of a Power station output
is over 1.8 A
...the current draw of ALL the Power station
outputs is over 1.8 A
Table 8
Generic Events (continued on next page) The Event numbers for
KYO 100
are those in brackets
(
....
)
14
If the Power station is not equipped with a Thermal probe, the preset output voltage will be 13.8 V. If the Power
station is equipped with a Thermal probe, the output voltage will depend on the probe temperature.
14
If the Power station is not equipped with a Thermal probe, the preset output voltage will be 13.8 V. If the Power
station is equipped with a Thermal probe, the output voltage will depend on the probe temperature.