Keypad Parameters
8 Keypad Parameters
The following table lists the inverter parameters related to EtherNet/IP and Modbus-
TCP communication features. Application types for each parameter is specified in the
“Protocol” column: E (EtherNet/IP) or M (Modbus TCP).
Setting Start/Stop:
Using the keypad, set DRV-06 parameter (C
md Source) to “4
(Field B
us)” if you want to operate (start/stop) the H2 inverter via communications.
Setting Frequency Reference:
Using the keypad, set DRV-07 parameter (Frq Ref
Src) to “7 (Field bBus)” if you want to provide the frequency reference via
commmunications.
Keypad parameters related to H2 communication board
Code
No.
Parameter Name
Initial
Value
Range
Description
Protocol
CNF-30
Option-1 Type
-
-
Displays the name of the
installed option board.
(Depending on the inverter OS
version, it may be displayed as
Reserved-18 instead of by
name.
E/M
DRV-06
Cmd Source
1
0
– 5 4: Set to “Field Bus.”
E/M
DRV-07
Freq Ref Src
0
0
– 11 7: Set to “Field Bus.”
E/M
COM-06
FBus S/W Ver
-
-
Indicates the version of the
installed option board.
E/M
COM-07
FBus ID
10
0
– 255
Set the station number of the
communication board.
E
COM-09
FBus Led
Displays the on/off status of the
LED indicators on the
communication board.
E/M
COM-10 Opt Parameter1
192
0
– 255
Sets the IP address.
E/M
COM-11 Opt Parameter2
168
0
– 255
COM-12 Opt Parameter3
1
0
– 255
COM-13 Opt Parameter4
101
0
– 255
COM-14 Opt Parameter5
255
0
– 255
Set the subnet mask.
E/M
COM-15 Opt Parameter6
255
0
– 255
COM-16 Opt Parameter7
255
0
– 255
COM-17 Opt Parameter8
0
0
– 255
COM-18 Opt Parameter9
192
0
– 255
Sets the Gateway address.
E/M
COM-19 Opt Parameter 10
168
0
– 255
COM-20 Opt Parameter 11
1
0
– 255
COM-21 Opt Parameter 12
10
0
– 255