Learning Basic Features
71
Lea
rni
890054-00-00
GM2 Series VFD
Acc/Dec Time Switch Frequency
You can set a switch frequency (Ad.60) to switch between 2 different Accel times and 2 different
Decel times. Parameters bA.70 (step accel time1) and bA.71 (step decel time1) are in effect below
the switch frequency. Parameters ACC (Accel time) and Dec (Decel time) are in effect above the
switch frequency.
Group Code
Name
Setting
Setting Range
Unit
Operation
ACC Acceleration time
5.0
0.0
–
600.0
sec
dEC Deceleration time
10.0
0.0
–
600.0
sec
bA
70
Multi-step
acceleration time 1
20.0
0.0
–
600.0
sec
71
Multi-step
deceleration time 1
20.0
0.0
–
600.0
sec
Ad
60
Acc/Dec time
transition frequency
30.00
0
–
Max Frequency
Hz
Acc/Dec Time Switch Frequency Setting Details
Code and
Features
Description
Ad.60
Acc/Dec time
transition
frequency
Set the Acc/Dec transition frequency (Ad.60). Acc/Dec gradients
configured at bA.70 and bA.
71 will be used when the inverter’s
operating frequency is at or below the switch frequency.
When the operating frequency exceeds the switch frequency, Acc/Dec
gradients configured at ACC and dEC will be used.
If you configure any of the P1
–
P5 digital input terminals for multi-step
Acc/Dec gradients (XCEL-L, XCEL-M, XCEL-H), Ad.60 Acc/Dec switch
frequency will not operate.
Содержание RSi GM2 Series
Страница 2: ...ii...
Страница 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Страница 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Страница 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Страница 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...