Learning Basic Features
51
Lea
rni
890054-00-00
GM2 Series VFD
Frequency Reference Configuration
The GM2 inverter provides several methods to setup and modify the frequency reference. Choices
include the keypad, analog inputs of voltage (V0 or V1) and current (I2), RS-485 (Modbus), or
Fieldbus option cards.
Group
Code
Name
Setting
Setting Range
Unit
Operation Frq
Frequency reference
source
0
KeyPad-1
0
–
8
-
1
KeyPad-2
2
V1
4
V0
5
I2
6
Int 485
8
Fieldbus
Set the Frequency Reference from the Keypad - Direct Input
You can modify the frequency reference using the keypad. Set parameter Frq (Frequency reference
source) in the Operations group to 0 (Keypad-1). Program the frequency reference at the 0.00
(Main screen) in the Operations group.
Group Code
Name
Setting
Setting Range
Unit
Operation
Frq
Frequency
reference source
0
KeyPad-1
0
–
8
-
0.00
Target frequency
0.00
Min to Max Frq*
Hz
* You cannot set a frequency reference that exceeds the Max. Frequency, as configured with dr.20.
Set the Frequency Reference from the Keypad - Using [
▲
] and
[
▼
] keys
You can use the [
▲
] and [
▼
] keys like a potentiometer to modify the frequency reference. Set
parameter Frq (Frequency reference source) in the Operations group 1 (Keypad-2). This allows the
frequency reference to be increased or decreased using the [
▲
] and [
▼
] keys at the 0.00 (Main
screen).
Group Code
Name
Setting
Setting Range
Unit
Operation
Frq
Frequency
reference source
1
KeyPad-2
0
–
8
-
0.00
Target frequency
0.00
Min to Max Frq*
Hz
* You cannot set a frequency reference that exceeds the Max. Frequency, as configured with dr.20.
Содержание RSi GM2 Series
Страница 2: ...ii...
Страница 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Страница 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Страница 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Страница 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...