GM2 Series VFD
Perform Basic Operations
890054-00-00
Actual Application Examples
Acceleration Time Configuration
The following demonstrates how to modify the Acceleration time (ACC) parameter value (from 5.0
to 16.0) in the Operation group.
Step
Instruction
Keypad Display
1
Ensure that the first code of the Operation group is selected, and
code 0.00 (Reference frequency) is displayed.
2
Press the [▲] key.
The display will change to the ACC code in the Operation group.
3
Press the [ENT] key.
The number "5.0" will be displayed, with "0" flashing. This indicates
that the current acceleration time is set to 5.0 seconds. The flashing
value is ready to be modified by using the keypad.
4
Press the [MODE/SHIFT] key to shift to the required units position
(ones, tens, hundreds, etc.).
"5" in the ones' place from "5.0" will flash. This indicates the
flashing value, "5" is ready to be modified.
5
To make the target value "16.0", press the [
▲
] key to change the
ones' place value to "6".
6
Press the [MODE/SHIFT] key to move to the tens' position.
"0" in the tens' place from "06.0" will flash.
7
To make the target value "16.0", press the [
▲
] key to change the
tens' value to "1", and then press the [ENT] key.
The selected value will flash on the display.
8
Press the [ENT] key again to save the changes.
"ACC" will be displayed. The change to the acceleration time setup
has been completed.
0.00
ACC
5.
0
5
.0
6
.0
0
6.0
16.0
ACC
Содержание RSi GM2 Series
Страница 2: ...ii...
Страница 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Страница 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Страница 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Страница 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...