![BENSHAW RSi GM2 Series Скачать руководство пользователя страница 149](http://html1.mh-extra.com/html/benshaw/rsi-gm2-series/rsi-gm2-series_instruction-manual_2735262149.webp)
Learning Advanced Features
890054-00-00
GM2 Series VFD
139
Changed Parameter Display
This feature displays all the parameters that are different from the factory defaults. Use this
feature to track changed parameters.
Group Code
Name
Setting
Setting
Range
Unit
dr
89
Changed parameter
display
0 View All
-
-
Changed Parameter Display Setting Details
Code and
Features
Description
dr.89
Changed Para
Configuration
Function
0
View All
Display all parameters
1
View Changed Display changed parameters only
Timer Settings
Add a timer function to one of the output relays. Set a digital input to activate the timer
and set On/Off delay times to one of the output relays.
Group Code
Name
Setting
Setting
Range
Unit
In
65~69
Px terminal setting
options
38
Timer In
0
–
52
-
OU
31
Multi-function
(digital) relay1 item
28
Timer Out
-
-
33
Multi-function
(digital) relay2 item
55 Timer On delay
3.00
0.00
–
100
sec
56 Timer Off delay
1.00
0.00
–
100
sec
Timer Setting Details
Code and
Features
Description
In.65~69 Px
Define
Choose one of the digital input terminals and set it to 38 (Timer In).
Ativate the terminal to start the timer function.
OU.31 Relay1,
OU.33 Relay 2
Set one relay to be used as a timer to 28 (Timer out).
OU.55
TimerOn Delay,
OU.56
TimerOff Delay
Set the On Delay time. When the digital input is activiated, the output
relay will change state after the On Delay time has passed.
Set the Off Delay time. When the digital input is de-activated, the
output relay will change state after the Off Delay time has passed.
Содержание RSi GM2 Series
Страница 2: ...ii...
Страница 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Страница 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Страница 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...