Learning Advanced Features
134
890054-00-00
GM2 Series VFD
2nd Motor Operation
2nd motor operation is used when a single inverter switches its output between two
motors. Parameters for the 2
nd
motor are set in the M2 parameter group. 2nd motor
operation is enabled when a digital input terminal defined as
“
2nd motor
”
function is
activated.
Group Code
Name
Setting
Setting
Range
Unit
In
65~69
Px terminal
setting options
26
2nd
Motor
0
–
52
-
2
nd
Motor Operation Setting Details
Code and
Features
Description
In.65
–
69 Px
Define
Set one of the digital input terminals (P1~P5) to 26 (2nd Motor) to
display the M2 (2nd motor) group. When activated, the inverter will
monitor and control the 2
nd
motor according to the settings listed
below. An external method of switching the inverter output between
the 2 motors is required.
NOTE:
When the inverter is in operation, switching of the digital input
will not be acknowledged.
Pr.50 (Stall Prevent) must be set first, before M2.28 (M2.Stall Lev)
settings can be used. Also, Pr.40 (ETH Trip Sel) must be set first, before
M2.29 (M2.ETH 1min) and M2.30 (M2.ETH Cont) settings.
Parameter Setting at Multi-function (digital) Terminal Input on a 2nd Motor
Code and Features
Description
Code
Description
M2.04 Acc Time
Acceleration time
M2.16 Inertia Rt Load inertia rate
M2.05 Dec Time
Deceleration time
M2.17 Rs
Stator resistance
M2.06 Capacity
Motor capacity
M2.18 Lsigma
Leakage inductance
M2.07 Base Freq Motor base frequency
M2.19 Ls
Stator inductance
M2.08 Ctrl Mode
Control mode
M2.20 Tr
Rotor time constant
M2.10 Pole Num
Pole number
M2.25 V/F Patt
V/F pattern
M2.11 Rate Slip
Rated slip
M2.26 Fwd Boost Forward Torque boost
M2.12 Rated Curr
Rated current
M2.27 Rev Boost Reverse torque boost
M2.13 Noload Curr
No-load Current
M2.28 Stall Lev
Stall prevention level
M2.14 Rated Volt
Motor rated voltage
M2.29 ETH 1min
Electronic thermal 1
minute rating
M2.15 Efficiency
Motor efficiency
M2.30 ETH Cont
Electronic thermal
continuous rating
Содержание RSi GM2 Series
Страница 2: ...ii...
Страница 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Страница 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Страница 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Страница 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...