Learning Advanced Features
114
890054-00-00
GM2 Series VFD
PID Operation Sleep Mode Setting Details
Code and Features
Description
AP.37 PID Sleep DT,
AP.38 PID Sleep
Freq
If an operating frequency lower than the value set in AP.38 is maintained for
the time set at AP.37, the operation stops and the inverter will enter sleep
mode.
AP.39 PID WakeUp
Lev,
AP.40 PID WakeUp
Mod
When in Sleep Mode, normal PID Control operation will resume when:
AP.40 -> 0 (Below Level)
: the feedback variable is less than the value set in
AP.39, PID WakeUp Lev setting.
AP.40 -> 1 (Above Level)
: the feedback variable is higher than the value set in
AP.39.
AP.40 -> 2 (Beyond Level):
the difference between the reference value and
the feedback variable is greater than the value set at AP.39.
PID Switching (PID Openloop)
When one of the multi-function (digital) terminals (In.65~69) is set to 23 (PID Openloop) and is
activated, PID operation stops and is switched to general operation. When the terminal is de-
activated, the PID operation resumes.
Note
When switching from PID operation to general operation, [%] values are converted to [Hz]
values. The normal PID output, PID OUT, is unipolar, and is limited by AP.29 (PID Limit Hi)
and AP.30 (PID Limit Lo). A 100.0% calculation of the PID OUT value is based on the dr.20
(MaxFreq) parameter setting.
Содержание RSi GM2 Series
Страница 2: ...ii...
Страница 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Страница 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Страница 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Страница 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...