Technical data
44
RCMA423AS_D00157_01_M_XXEN/08.2016
Measuring current transformer connecting cable
RCMA423AS accessories
Mounting clip for screw mounting (1 piece per device) .......................................................................... B 9806 0008
Measuring current transformers accessories
Snap-on mounting for DIN rail: W20AB /W35AB(P) ...............................................................................B 9808 0501
Snap-on mounting for DIN rail: W60AB(P) ...............................................................................................B 9808 0502
6.4
Error codes
Should, contrary to all expectations, a device error occur, error codes will ap-
pear on the display. Typical error codes are described below:
Type
Length (m)
Art. No.
WX-100
1
B 9808 0503
WX-250
2,5
B 9808 0504
WX-500
5
B 9808 0505
WX-1000
10
B 9808 0506
Error code
Meaning:
E.01
Fault CT connection monitoring
Appropriate action
: Check CT connection for short-circuit
or interruption. After eliminating the fault, the error code
will be automatically deleted.
E.02
Fault CT connection monitoring
during manual self test.
Appropriate action
: Check CT connection for short-circuit
or interruption. After eliminating the fault, the error code
will be automatically deleted.
E…
Appropriate action when error codes > 02 occur:
Appropriate action
: Carry out a reset. Reset the device to
factory setting. After eliminating the fault, the error code
will be automatically deleted. If the fault continues to exist,
please contact the Bender Service.