![Bender RCMA420 Скачать руководство пользователя страница 17](http://html1.mh-extra.com/html/bender/rcma420/rcma420_manual_2731735017.webp)
Installation and connection
17
RCMA420_D00059_04_M_XXEN/05.2021
The front plate cover is easy to open at the lower part marked by an arrow.
1.
DIN rail mounting
Snap the rear mounting clip of the device into place in such a way that
a safe and tight fit is ensured.
Screw fixing
Use a tool to move the rear mounting clips (a second mounting clip
required, see ordering information) to a position that it projects bey-
ond the enclosure. Then fix the device using two M4 screws.
2.
Wiring:
Connect the device according the wiring diagram.
Terminal
Connections
A1, A2
Connection to supply voltage
1
Socket for the connecting cable CTX… to the measuring CT
T/R
Connection to the combined test/reset button
11, 12, 14
Alarm relay K1
21, 22, 24
Alarm relay K2
U
s
+12V
–12V T
GND
S1(k) S2(l)
CTUB101-
CTBC...
–12V k
T
l
GND
+12V
1
CTX...
AL1
AL2
T/R
1
T/R
A1
14
11 12
24
21 22
A2