Operation
46
PEM735_D00084_00_M_XXEN/02.2015
6.9 Setup: adjustment possibilities
The table illustrates the display screens, their meaning and the adjustment
possibilities.
Display screen
Level 1
Level 2
Parameters
Description
Adjustment
possibilities
Default
setting
PROGRAMMING
Setup mode
PASWORD
Password
Enter password
/
0
PAS SET
Change password?
YES/NO
NO
NEW PAS New password
Enter new password
0000…9999
0
SYS SET
System settings
YES/NO
NO
TYPE Wiring mode
Select wiring mode
WYE/DELTA/
DEMO
WYE
PT
Voltage transfor-
mer
Select voltage transfor-
mer transformation ratio
1…10,000
1
CT
Measuring current
transformers
Select CT transformation
ratio
1…30,000 (1 A)
1…6,000 (5 A)
1
I4 Neutral current
Select CT transformation
ratio for
I
4
1…10,000
1
PF SET Power factor rule
Power factor rule
*
IEC/IEEE/-IEEE
IEC
KVA SET S calculation method **
V/S
V
HD SET Harmonic distortion calculation method ***
FUND/RMS
FUND
V NOM Nominal voltage
U
nom
(equals
U
LL
)
100…700 (V)
100
Hz NOM Nominal frequency
f
nom
50/60 (Hz)
50
I1 REV I
1
CT
Reverse phase
I
1
CT polarity
YES/NO
NO
Содержание LINETRAXX PEM575 Series
Страница 8: ......
Страница 12: ...Making effective use of this document 12 PEM735_D00084_00_M_XXEN 02 2015 ...
Страница 28: ...Installation and connection 28 PEM735_D00084_00_M_XXEN 02 2015 ...
Страница 62: ...Application inputs and outputs 62 PEM735_D00084_00_M_XXEN 02 2015 ...
Страница 82: ...Logging 82 PEM735_D00084_00_M_XXEN 02 2015 ...
Страница 88: ...Power Quality 88 PEM735_D00084_00_M_XXEN 02 2015 ...
Страница 162: ...Modbus Register Map 162 PEM735_D00084_00_M_XXEN 02 2015 ...
Страница 166: ...Technical data 166 PEM735_D00084_00_M_XXEN 02 2015 ...
Страница 170: ...INDEX 170 PEM575_D00016_00_M_XXEN 04 2015 ...
Страница 171: ......