Installation and connection
26
PEM735_D00084_00_M_XXEN/02.2015
4.7.3
Connection via voltage transformers
The coupling via voltage transformers allows the use of the measuring device in
medium and high voltage systems.
The transformation ratio can be adjusted in the PEM575 (1…2200).
Fig. 4.7: Connection diagram 3-wire system via voltage transformers
4.8 Digital inputs
The universal measuring device PEM575 provides 6 digital inputs. The inputs are
supplied by a galvanically isolated DC 24 V voltage. An external circuit providing at
least a current of
I
min
> 2.4 mA is required for triggering the inputs.
L1
L2
L3
N
PEM
R
i
LV / MV / HV
DI1
DIC
DI5
DI6
DI2
DI3
DI4