Quick start: PEM555

PEM555_D00016_00_Q_XXEN/04.2014

This short operating instruction does not replace the manual!

You will find the manual on the website

www.bender.de

Make sure that the personnel has read this manual and under-
stood all instructions relating to safety.

Quick start

Intended use

Scope of delivery

The universal measuring device PEM555 is suitable for 

the analysis of energy and power (Power Analyzer)

monitoring of the power supply quality (Power Quality) 

data recording for energy management (Energy Manage-
ment). 

As a compact device for front panel mounting, it is suitable to re-
place analogue indicating instruments. The PEM555 is suitable for
3 and 4-wire systems and can be used in TN, TT and IT systems.
The current measurement inputs of the PEM are connected via
external ../1 A or ../5 A measuring current transformers. 

Measurement in medium and high-voltage systems are principal-
ly carried out using measuring current and voltage transformers.
The accuracy of the active energy metering corresponds to class
0.2 S in compliance with the DIN EN 62053-22  (VDE 0418 Part 3-
22):2003-11.

1 PEM555

Safety instructions

This short operating instructions

1 sealing frame "IP54"

Safety instruction

Danger of electric shock!

Follow the basic safety rules when working with electricity. 

Consider the data on the rated voltage and supply voltage

 as

specified in the technical data!

Installing the device

Front-panel mounting (front view, side view, panel cutout)

A front-panel cutout of 92 mm x 92 mm is required for the device.

1.

Insert the device into the installation opening of the front panel.

2.

Insert the two installation clips into the equipment rail from behind.

3.

Push the installation clips towards the front panel and tighten the screws by hand.

4.

Check the device to ensure that it is firmly mounted in the front panel.

92

92

 

96

106

88

96

91

18

88

91

18

96

Содержание LINETRAXX PEM555

Страница 1: ...A measuring current transformers Measurement in medium and high voltage systems are principal ly carried out using measuring current and voltage transformers The accuracy of the active energy metering corresponds to class 0 2 S in compliance with the DIN EN 62053 22 VDE 0418 Part 3 22 2003 11 1 PEM555 Safety instructions This short operating instructions 1 sealing frame IP54 Safety instruction Dan...

Страница 2: ...ms both phase conductors have to be protected DI1 DI6 DIC Digital inputs DO13 DO14 DO23 DO24 DO33 DO34 Digital outputs N O contacts I11 I12 I21 I22 I31 I32 Connection to the system to be monitored D D SH Connection RS 485 bus L1 L2 L3 N Measuring voltage inputs The measuring leads should be protected with appropriate fuses Modbus TCP Pin assignment 1 Transmit Data 2 Transmit Data 3 Receive Data 4 ...

Страница 3: ... the parameters for modification confirms parameter change Data display via buttons Data display via communication interface A large number of measuring values can be obtained from the device via the buttons without having to use the communications interface Which button is to be activated to obtain the individual values is described in more detail in the manual All measuring values can be obtaine...

Страница 4: ...nbalance unb phase angle for voltages and cur rents demands Description of standard display indications areas 1 3 and 4 Standard display indications Area Segments Symbol description 1 DI open DI closed DO open DO closed 3 V kV A Hz Measurement units for U I THD f kW MW kvar kVA MVA Measurement units for P Q S Current value expressed as a percentage inductive capacitive C1 Status commu nications in...

Отзывы: