![Bender ISOMETER isoNAV685-D-B Скачать руководство пользователя страница 46](http://html.mh-extra.com/html/bender/isometer-isonav685-d-b/isometer-isonav685-d-b_manual_2731673046.webp)
Technical data
Technical data
isoNAV685-D-B_D00264_03_M_XXEN/06.2017
46
Push-wire terminals X1:
Nominal current................................................................................................................................................................................. ≤ 8 A
Conductor sizes.........................................................................................................................................................................AWG 24-16
Stripping length............................................................................................................................................................................... 10 mm
rigid/flexible .......................................................................................................................................................................0.2…1.5 mm²
flexible with ferrule without plastic sleeve......................................................................................................................0.25…1.5 mm²
flexible with TWIN ferrule with plastic sleeve ...............................................................................................................0.25…0.75 mm²
Other
Operating mode........................................................................................................................................................ continuous operation
Mounting (0°) .........................................................................................display oriented, cooling slots must be ventilated vertically
5)
Degree of protection internal components .........................................................................................................................................IP40
Degree of protection terminals ...........................................................................................................................................................IP20
DIN rail mounting acc. to.............................................................................................................................................................IEC 60715
Screw fixing ..................................................................................................................................................... 3 x M4 with mounting clip
Enclosure material................................................................................................................................................................polycarbonate
Flammability class................................................................................................................................................................................. V-0
ANSI code ............................................................................................................................................................................................... 64
Dimensions (W x H x D) .............................................................................................................................................. 108 x 93 x 110 mm
Weight ........................................................................................................................................................................................... < 390 g
1)
At a frequency > 200 Hz, the connection of X1 must be insulated. Only permanently installed devices which at least have over-
voltage category CAT2 (300V) may be connected.
2)
Indication limited outside the temperature range -25…+55 °C.
3)
U
s
[Volt] = supply voltage ISOMETER®
4)
This is a class A product. In a domestic environment, this product may cause radio interference. In this case, the user may be
required to take corrective actions.
5) Recommendation: Devices mounted at 0 ° (display-oriented, cooling slots must be ventilated vertically).
For devices mounted at an angle of 45°, the max. working temperature is reduced by 10 °C.
For devices mounted at an angle of 90°, the max. working temperature is reduced by 20 °C.
15.2 Standards and certifications
The ISOMETER® has been developed in compliance with the following standards:
• DIN EN 61557-8 (VDE 0413-8):2015-12
• IEC 61557-8:2014-12
• IEC 61557-8:2014/COR1:2016
• DIN EN 61557-8 Ber 1 (VDE 0413-8 Ber 1):2016-12