Display
Display
isoNAV685-D-B_D00264_03_M_XXEN/06.2017
25
8.4 Acknowledge fault memory
In order to acknowledge the fault message and return to the ISOMETER®'s standard
display, all faults must be acknowledged by means of the reset button.
This means that fault messages can only be reset when the cause of the fault has been
eliminated.
Press the reset button, then and OK to clear the fault memory.
The ISOMETER® then returns to the standard display.
RESET
3.2
Reset current
messages? All
messages are
saved in the
history memory.
Cancel
RESET
8.5 History memory
Up to 1023 alarm messages and device errors are stored in the history memory with date
and time stamp. When the history memory is deleted, the minimum insulation resistance
R
min
will also be reset under Menu/ Data Measured values - Data insulation - Reset.
Historie 4.1
Isolationsfehler
11kΩ
28.03.14
17:02
28.03.14
17:18
8/8
Next message
Leave view
Fault description
Alarm value
Feault occured
Fault disappeared
Previous message
Number of selected
errors/
Total number of
error messages