![Bender ISOMETER isoHV525 Скачать руководство пользователя страница 33](http://html.mh-extra.com/html/bender/isometer-isohv525/isometer-isohv525_manual_2731666033.webp)
Data access to the isoHV525-S4-4 using the Modbus RTU protocol
33
isoHV525_D00297_04_M_XXEN/05.2018
7.3 Exception code
If a request cannot be answered for whatever reason, the ISOMETER® will send a so-
called exception code with which possible faults can be narrowed down.
7.3.1
Structure of the exception code
Exception code
Description
0x01 Impermissible
function
0x02
Impermissible data access
0x03
Impermissible data value
0x04
Internal fault
0x05
Acknowledgement of receipt (answer will be time delayed)
0x06
Request not accepted (repeat request if necessary)
Byte Name
Example
Byte 0
ISOMETER® Modbus address
0x03
Byte 1
Function code (0x03) + 0x80
0x83
Byte 2
Data (exception code)
0x04
Byte 3, 4
CRC16 checksum
0xE133