isoHV525-S4-4 parameter overview
27
isoHV525_D00297_04_M_XXEN/05.2018
5.2.1
Alarm assignment
"
r1
"
and
"
r2
"
In the alarm assignment, each notification/alarm is assigned to the corresponding relay
with the setting "on". In the event of an unsymmetrical insulation fault, only the alarm
corresponding to the assigned and affected conductor (L1/+ or L2/-) will be set.
FAC
= Factory setting;
Cs
= Customer setting
* Value can be read only. Assigning a new value is not possible.
5.2.2
Fault memory configuration
FAC
= Factory setting;
Cs
= Customer setting
K1 „r1“
K2 „r2“
Alarm description
Available via
FAC
Cs
FAC
Cs
BMS
Modbus
off
on
Device error E.xx
X*
X
on
off
Pre-alarm R1
Fault
R
F
on L1/+
X*
X
on
off
Pre-alarm R1
Fault
R
F
on
L2/-
X*
X
off
on
Alarm R2
Fault
R
F
on
L1/+
X*
X
off
on
Alarm R2
Fault
R
F
on L2/-
X*
X
off
on
Alarm
U
n
Undervoltage
X*
X
off
on
Alarm
U
n
Overvoltage
X*
X
off
off
Manually started device test
X
off
off
Device start with Alarm (S.AL)
X
FAC
Cs
Description
Available via
BMS
Modbus
off
Memory function for alarm messages
(fault memory)
X
X