Modbus register assignment of the ISOMETER®
8. Modbus register assignment of the ISOMETER®
Depending on the device condition, the information in the registers is the measured
value without alarm; the measured value with alarm 1; the measured value with alarm 2;
or only the device error.
( ) = Channel description code (refer to
[ ] = Alarm type (refer to
Register
Measured value
Device error
Without alarm
Alarm 1
Alarm 2
1000
to
1003
R
F
Insulation fault (71)
[no alarm]
R
F
Insulation fault (1)
[prewarning]
R
F
Insulation fault (1)
[alarm]
---
Connection earth
(102)
[Device error]
1004
to
1007
---
---
---
---
1008
to
1011
U
n
Voltage (76)
[no alarm]
U
n
Overvoltage
(78) [alarm]
---
Connection to sys-
tem (101)
[Device error]
1012
to
1015
C
e
capacitance (82)
[no alarm]
---
---
---
1016
to
1019
U
L+e
Voltage (76)
[no alarm]
U
n
Undervoltage
(77) [alarm]
---
---
1020
to
1023
U
L-e
Voltage (76)
[no alarm]
---
---
---
1024
to
1027
Fault location in %
--- (1022)
[no alarm]
---
---
---
1028
to
1031
---
---
---
---
1032
to
1035
Measured value
update counter
--- (1022)
[no alarm]
---
---
---
Device error (115)
[Device error]
Register
Property
Description
Format
Unit
Value range
3000
RW
Reserved
---
---
---
3001
RW
Pre-alarm value resis-
tance measurement
"R1"
UINT 16
kΩ
R2 … 5000
3002
RW
Reserved
---
---
---
3003
RW
Alarm value resis-
tance measurement
"R2"
UINT 16
kΩ
10 … R1
3004
RW
Reserved
---
---
---
3005
RW
U
BattH
specified bat-
tery value, upper limit
UINT 16
V
U
BattL
… 500
3006
RW
Reserved
---
---
---
3007
RW
U
BattL
specified bat-
tery value, lower limit
UINT 16
V
3 … U
BattH
3008
RW
Reserved
---
---
---
3009
RW
U
CrossH
cross fault
upper limit
UINT 16
V
U
CrossL
… 500
3010
RW
Reserved
---
---
---
3011
RW
U
CrossL
cross fault
lower limit
UINT 16
V
3 … U
CrossH
3012
RW
Memory function for
alarm messages
(Fault memory) "M"
UINT 16
---
0 = Inactive
1 = Active
3013
RW
Operating mode of
alarm relay 1 "r1"
UINT 16
---
0 = n.o.
1 = n.c.
3014
RW
Operating mode of
alarm relay 2 "r2"
UINT 16
---
0 = n.o.
1 = n.c.
3015
RW
Bus address "Adr"
UINT 16
---
0 / 3 … 90
3016
RW
Baud rate "Adr 1"
UINT 16
---
0 = BMS
1 = 1.2 k
2 = 2.4 k
3 = 4.8 k
4 = 9.6 k
5 = 19.2 k
6 = 38.4 k
7 = 57.6 k
8 = 115.2 k