Settings
Settings
iso685-D-P_D00170_00_M_XXDE/06.2016
63
10.2 Factory settings
Parameter
Value
Response values/alarms
Response value R
an1
(ALARM 1)
40 kΩ
Response value R
an2
(ALARM 2)
10 kΩ
DC alarm
off
DC-offset voltage for DC alarm
65 V
Fault memory
off
Coupling monitoring
on
Time response
Start-up delay T
start-up
≤ 0 s
Digital inputs
Digital input 1
Mode (Operating mode)
Active high
Function
Test
Digital input 2
Mode (Operating mode)
Active low
Function
Reset
Digital input 3
Mode (Operating mode)
Active high
Function
Deactivate device
Digital outputs
Digital output 1
Function 1
Common alarm EDS
Function 2
off
Function 3
off
Interfaces
DHCP
off
IP address
192.168.0.5
Net mask
255.255.255.0
BCOM address
system-1-0
Device address BS bus
1
Switching elements
Relay 1
Test
on
Operating mode
N/C operation
Function 1
Ins. alarm 1
Function 2
Connection fault
Function 3
off
Relay 2
Test
on
Operating mode
N/C operation
Function 1
Ins. alarm 2
Function 2
Device fault
Function 3
Connection fault
EDS
Mode
auto
Current
10 mA
Parameter
Value