8.6 History memory
Up to 1023 alarm messages and device errors are stored in the history memory with date
and time stamp. When the history memory is deleted, the minimum insulation resistance
R
min
will also be reset at Menu/Data Measured values - Data insulation.
History
4.1
Insulation fault
11kΩ
28.03.14
17:02
28.03.14
17:18
8/8
PGH ON
Next message
Leave view
Fault description
Alarm value
Feault occured
Fault disappeared
Previous message
Number of selected
errors/
Total number of
error messages
8.7 Insulation fault location
When EDS mode is activated, the ISOMETER® indicates the message "Ins. fault locat.". Be-
low, on the left side it indicates which EDS mode is activated. On the right side it indicates
the polarity change of the measuring pulses including the pause in between .
An active fault is displayed by
. The upper part of the display will become orange and
displays the fault message. The alarm LEDs are lit. If several fault messages have ap-
peared, you can navigate through the faults using the and buttons.
Positive measuring pulse
Pause
Negative measuring pulse
The insulation fault location has been started manually and runs con-
tinuously.
No insulation measurement takes place.
43 s
Insulation fault location in auto mode and 1 cycle.
Time countdown of a measurement cycle.