Commissioning
7. Commissioning
7.1 General initial commissioning process
1.
Check that the ISOMETER® is properly connected to the system to be monitored.
2.
Connect the supply voltage to the ISOMETER®. Adjust the device using the commis-
sioning wizard. Afterwards, the ISOMETER® performs a self test in four steps. The
alarm relays are not checked during this test. After completion of the test, the meas-
ured insulation resistance is shown on the display. If the value exceeds the response
values indicated in the bottom line of the display, the message "OK" will additionally
be displayed.
3.
Check the ISOMETER® in the system being monitored, e.g. using a suitable resistance
to earth
After setting the response value Ran2 for alarm 2, the device starts a self test, makes the
first measurement and outputs the measured insulation resistance values of the IT sys-
tem being monitored, then commissioning is completed.
Commissioning pocedure - iso685-x(-B)
For customer-specific configured devices, the commissioning wizard
might be deactivated and cannot be run. In this case, the device is preset.
However, the commissioning wizard can be started as described at „Reco-
missioning“ .
Observe device status!
The device is in an alarm state until initial commissioning has been com-
pleted.
Step
ISOMETER
®
commissioning
1.
Connect the device according to the wiring diagram and device documentation
2.
Connect the supply voltage
3.
Connect the mains voltage
4.
Run through commissioning wizard
5.
The ISOMETER® performs a self tes
6.
Execute a function test with a suitable resistance between the system and earth.
7.
Remove the resistance
8.
Adjust the basic settings if necessary
9.
The ISOMETER® is properly connected and functions reliably
7.2 Initial commissioning
Follow the instructions of the commissioning wizard on the display.
7.2.1 Setting language
The language selected here will be used in the menu and for device messages.
7.2.2 Setting date and time
Alarm messages in the history memory and the insulation resistance value over time can
only be assigned correctly to the isoGraph when date and time are set correctly.
Check network function!
When the device has been integrated into a network, the influence on the
network has to be checked with the device switched on and off.
Language
x.6.2
• Deutsch
o English
o ...
Date
x.6.4
28.07.2016
Min.
Max.
1
12
Commissioning
x.6
2/1x
Please set the current
date and time.