Curve 6:
When the system leakage capacitances are greater than the maximum per-
missible value for
C
e
, as shown in curve 5, the response sensitivity decreases.
The indication of the test current on the IRDH575 display in case of high sys-
tem leakage capacitance also changes.
When considering the curves, a point to be taken into account is that the sum
of the pre-capacitances upstream of the individual measuring current trans-
former must amount to at least 50 % of the maximum total capacitance.
Otherwise, it may result in wrong alarm messages.
A value of 300 µFV/230 V = 1.3 µF is taken to be the maximum system leakage
capacitance value. When the limiting value is exceeded, false tripping may
occur.