Programming examples mode 2
81
The Modbus RTU Master addresses BMS address 29, 107TD47, for information about the ac-
tual load of the transformer (operating message). This value is available at channel 2 of the
device:
The Modbus RTU Master sends an appropriate command to FTC470XMB
(function 16, output data):
The 107TD47 replies that the transformer utility is 66% (function 3, input data)
Word 1
Word 2
Word 3
Word 4
Word 5
H-Byte
L-Byte
H-Byte
L-Byte
H-Byte
L-Byte
H-Byte
L-Byte
H-Byte L-Byte
always
„0“
Consecutive
Modbus ID
No.
BMS address of
the addressed
device
BMS
channel
No.
always
„0“
BMS
com-
mand
always
„0“
BMS
data
type
BMS data value
0
9
29
2
0
4
0
0
0
Word 1
Word 2
Word 3
Word 4
Word 5
0
9
29
2
0
4
0
65
66