Function
54
6.5.13 Requesting the operating mode of the alarm relay
Writing to
FTC470XMB (= output data of the Modbus RTU Master)
Table 6.39: Master request: operating mode of the collective alarm relay
Reading from
FTC470XMB (= input data of the Modbus RTU Master)
Table 6.40: FTC reply to: operating mode of the collective alarm relay
6.5.14 Setting the operating mode of the alarm relay
Writing to
FTC470XMB (= output data of the Modbus RTU Master)
Table 6.41: Master request: setting the operating mode of the alarm relay
Reading from
FTC470XMB (= input data of the Modbus RTU Master)
Table 6.42: FTC reply to: setting the operating mode of the alarm relay
Function
Devices
Word 2
Word 3
Word 4
Word 5
BMS
address
Chann
el No.
„0“
BMS
comma
nd
„0“
Data
type
Data
value
Request for the operating mode of the col-
lective alarm relay
EDS..,
RCMS..,
PRC470
address
0
0
27
0
0
0
N/O operation
EDS..,
RCMS..,
PRC470
Address
0
0
27
0
1
0
N/C operation
„
„
0
0
27
0
1
1
Invalid value
„
„
0
0
27
0
255
255
Function
Devices
Word 2
Word 3
Word 4
Word 5
BMS
address
Chann
el No.
„0“
BMS
comma
nd
„0“
Data
type
Data
value
Setting the alarm relays to N/O operation
107TD47
EDS...,
RCMS...,
PRC470
address
0
0
25
0
1
0
Setting the alarm relays to N/C operation
„
„
0
0
25
0
1
1
Acknowledgement
EDS..,
RCMS..,
PRC470
Address
0
0
25
0
1
Value
Invalid value
„
address
0
0
25
0
255
255