Function
35
6.1.2 Requesting alarm messages via the channel number
Writing to
FTC470XMB (= output data of the Modbus RTU Master)
Table 6.3: Master request: request for alarm messages via channel number
Reading from
FTC470XMB (= input data from the Modbus RTU Master)
Function
Devices
Word 2
Word 3
Word 4
Word 5
BMS
address
channe
l No.
„0“
BMS
comma
nd
„0“
Data
type
Data
value
Request for alarm messages via the channel
number
all
address
Chan-
nel No.
0
2
0
0
0
No alarm messages
all
Address
Chan-
nel No.
0
2
0
1
0
Insulation fault in the IT system
MK2418-11
SMI470-9
„
1
1
0
2
0
11
1
Transformer overload
MK2418-11
SMI470-9
„
2
2
0
2
0
11
2
Transformer overtemperature
107TD47
IZ427
MK2418-11
SMI470-9
„
3
3
3
3
0
2
0
11
3
Failure Line 1
PRC487
MK2418-11
SMI470-9
„
1
4
4
0
2
0
11
4
Failure Line 2
PRC487
MK2418-11
SMI470-9
„
2
5
5
0
2
0
11
5
Insulation fault operating theatre lamp
107TD47
MK2418-11
SMI470-9
„
8
6
6
0
2
0
11
6
Failure distribution board (Line 3, down-
stream the switchover module)
PRC487
MK2418-11
SMI470-9
„
3
8
8
0
2
0
11
8
Failure AV line
PRC487
„
1, 2
0
2
0
11
25
Failure AV line
PRC487
„
1, 2
0
2
0
11
26
Failure AV line
PRC487
„
1, 2
0
2
0
11
27
Failure N conductor
PRC487
„
4
0
2
0
11
29
Short circuit distribution board
PRC487
„
10
0
2
0
11
30
Phase sequence left
ATiCS
„
30
0
2
0
11
39
Failure BSV line
(Battery-backed power supply system)
ATiCS
„
1, 2
0
2
0
11
40
Connection fault system
107TD47
IRDH...
„
4
3
0
2
0
12
101
Connection fault PE
107TD47
IRDH...
IZ427
„
5
4
5
0
2
0
12
102
Short circuit CT input
107TD47
EDS46x/49x
IZ427
RCMS460
RCMS490
„
6
1...12
6
1...12
1...12
0
2
0
12
103