Web server application examples
53
7.3 Monitoring an IRDH275B connected to the BMS bus
The menus and submenus are selected using the BMS Ex-
plorer. The standard menus, as illustrated opposite, pro-
vide an overview about the configuration and the current
measuring values of a system consisting of bus-capable de-
vices. An administrator password is not required for device
monitoring.
Submenu: Current values
Alarm messages
(highlighted red, if
available)
Measured insulation resist-
ance in k
Ω
Channel 1 / channel 2
= scanned BMS channels
TEST
= indication that the
alarm has been trig-
gered by a self test.
Operating messages
Measured insulation resist-
ance in k
Ω
Channel 1 / channel 2
= scanned BMS channel
Measured system leakage
capacitance in
μ
F
Channel 3
= scanned BMS channel
Submenu: Device information
Device type
e.g.: IRDH275B-4
Software version
Version No.
Response Value Alarm 1
Response Value Alarm 2
Thresholds in k
Ω
. IRDH275 outputs alarm messages when the
values exceed or fall below the limit values.
Relay mode 1
Relay mode 2
N/O or N/C operation
N/O / N/C operation Test
Flash (relays switch with a cycle of 0.5 Hz)
Measuring principle
AMP / DC
Analog output
0/4...20 mA
External coupling unit
on/off
Max. leakage capacitance
150 μF / 500 μF
Self test
Period of time between two tests: 24 h / 1 h / Off
Time of test
Beginning of the self test: 00.00 h...23.00 h
Language
D / GB
Fault memory
on/off
Содержание FTC470XET
Страница 10: ...Safety instructions 10 TGH1375en 02 2010...
Страница 18: ...The FTC470XET protocol converter 18 TGH1375en 02 2010...
Страница 56: ...Web server application examples 56 TGH1375en 02 2010...
Страница 78: ...Technical data 78 TGH1375en 02 2010...
Страница 80: ...Frequently asked questions 80 TGH1375en 02 2010...
Страница 83: ......