Web server application examples
46
7.1.1
Calculating actual measured values
The actual measuring values of a circuit monitored by a CT are to be calculated. The CT itself
is monitored by an RCMS470-12 with BMS address 5. The measuring signal is connected to
channel 2.
1. Select: "Address 5: RCMS470-12“ from the main menu. The respective setting submenu will appear.
2. Now click on "Current values". A list appears where you can read off the currently measured value for
channel 2. You will also be informed about the location of the CT and that a residual current is flow-
ing.
7.1.2
Retrieving device information
An RCMS470-12 with BMS address 5 has to be parameterised again after making changes in
an electrical system. The current status of the function, of the response values and the CT
connection monitoring have to be determined for this purpose. This data is available,
amongst other data, in the "device information" window.
1. Select: "Address 5: RCMS470-12“ from the main menu. The submenu required to carry out settings
will appear.
2. Click on "device information". A list appears, representing data of all channels.
Submenu: System description
Channel 1 to 12:
Function
Measuring point, alarm text
Text
New text