11
3. Bus coupling
BENDER devices with bus interface communicate with each other via the Bender measuring
device interface (BMS bus). The FTC470XET allows data exchange between the BMS bus and
TCP/IP based networks via Ethernet.
This protocol converter enables you to query and parameterise Bender devices connected to
the BMS bus or single user PCs via Internet or local computer networks.
3.1 Minimal system
At least, the following components are required to operate an FTC470XET:
z
A network-capable computer with Ethernet connection and a frame-capable Web browser. The
FTC470XET user interface has been optimised for displays with a resolution of 1024 x 768 pixels.
z
An Ethernet connection with a cross over patch cable, STP,
RJ45 plug.
z
Suitable IP addresses for communication between the computer and the FTC470XET. Both devices
must have IP addresses of the same address range and identical network masks.
Fig. 3.1: Minimal system to operate an FTC470XET
120
W
A
B
max. 1200 m
B
A
120
W
FTC470XET
Bender measuring device interface (BMS bus)
TCP/IP via Ethernet
Web
browser
RJ45, Cross over
Web server
10 Mbit/s
BMS
RS485
OPC server
FTP server