Programming examples
66
FTC470XDP_D00111_00_M_XXEN/02.2015
The PROFIBUS Master deletes all alarm messages of an RCMS470-12 residual current evaluator with
address 10.
PROFIBUS Master output data:
The existing alarms of the RCMS470-12 are being deleted and acknowledged.
PROFIBUS Master input data:
The PROFIBUS Master introduces an internal self test of a 107TD47 insulation monitoring device with
address 3.
PROFIBUS Master output data:
The 107TD47 carries out a self test and acknowledges it.
PROFIBUS Master input data:
The PROFIBUS Master mutes the buzzer of an MK2418 alarm indicator and test combination with ad-
dress 22.
PROFIBUS Master output data:
MK2418 acknowledges the buzzer mute (software 2.0 or higher).
PROFIBUS Master input data:
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
Consecutive
PROFIBUS ID
No.
always
"0"
BMS address of
the addressed
device
BMS channel
number
BMS
Com-
mand
BMS data
type
High byte
BMS data
value
Low byte
BMS data
value
15
0
10
0
13
0
0
0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
15
0
10
0
13
0
0
0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
Consecutive
PROFIBUS ID
No.
always
"0"
BMS address of
the addressed
device
BMS channel
number
BMS
Com-
mand
BMS data
type
High byte
BMS data
value
Low byte
BMS data
value
16
0
3
0
8
0
0
0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
16
0
3
0
8
0
0
0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
Consecutive
PROFIBUS ID
No.
always
"0"
BMS address of
the addressed
device
BMS channel
number
BMS
Com-
mand
BMS data
type
High byte
BMS data
value
Low byte
BMS data
value
17
0
22
0
14
0
0
0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
17
0
22
0
14
0
0
0