Function
52
FTC470XDP_D00111_00_M_XXEN/02.2015
6.9 Control commands for use in BMS Master mode
6.9.1
Deleting all alarm messages
Writing to FTC470XDP (= output of the PROFIBUS Master):
Table 6.61: Master request: deleting all alarm messages
Reading from FTC470XDP (= input data of the PROFIBUS Master):
Table 6.62: FTC reply to: deleting all alarm messages
6.9.2
Starting a self test of insulation monitoring devices
Writing to FTC470XDP (= output of the PROFIBUS Master):
Table 6.63: Master request: starting the self test of an insulation monitoring device
Reading from FTC470XDP (= input data of the PROFIBUS Master):
Table 6.64: FTC reply to: starting a self test of an insulation monitoring device
When the FTC470XDP works in the BMS Slave mode, a temporary Master takeo-
ver is required before carrying out the control commands below!
Take into consideration that the Master function must be returned by the
FTC470XDP after Master function transfer and after the control commands have
been carried out.
Function
Devices
Channel
No.
BMS
comma
nd
Data
Type
Data
Value
Deleting all alarm messages
all
0
13
0
0
Acknowledgement that all alarm messages are deleted
RCMS…,
0
13
0
0
No answer
EDS…
0
13
255
255
Function
Devices
Channel
No.
BMS
comma
nd
Data
Type
Data
Value
Starting the self test of an insulation monitoring
device
107TD47,
IRDH375B/
575,
MK2418-11,
SMI470-9
0
8
0
0
Self test is being acknowledged
107TD47..,
MK2418-
11, SMI470-9
0
8
255
255