6.8 Requesting device-specific information
6.8.1
Requesting fault messages after a self test
Writing to FTC470XDP (= output of the PROFIBUS Master)
Table 6.55: Master request: fault messages after a self test
Reading from FTC470XDP (= input data of the PROFIBUS Master)
Table 6.56: FTC reply to: fault messages after a self test
6.8.2
Requesting the software version
Writing to FTC470XDP (= output of the PROFIBUS Master)
Table 6.57: Master request: for the software version
Reading from FTC470XDP (= input data of the PROFIBUS Master)
Table 6.58: FTC reply to: the software version
When the FTC470XDP works in the BMS Slave mode, a temporary Master takeo-
ver is required before carrying out the parameterization below!
Take into consideration that the Master function must be returned by the
FTC470XDP after Master function transfer and the parameterization.
Function
Devices
Channel
No.
BMS
comma
nd
Data
Type
Data
Value
Request for fault messages after a self test
channel
No.
9
1
0
No fault detected
EDS..,
RCMS…
1… 12
9
1
0
Input not connected, no CT connected
EDS..,
RCMS…
1… 12
9
22
0
No CT connected
EDS..
1… 12
9
22
0
Input switched off
EDS..,
RCMS…
1… 12
9
21
0
Input short-circuited
EDS..,
RCMS…
1… 12
9
23
0
No more channels
1… 12
9
254
254
Invalid value
EDS..,
RCMS…
1… 12
9
255
255
Function
Devices
Channel
No.
BMS
comma
nd
Data
Type
Data
Value
Request for the software version
all
0
22
0
0
Number of the device software version x 100.
Example: answer 112 = V 1.12.
all
0
22
1
Version
x 100