Function
39
FTC470XDP_D00111_00_M_XXEN/02.2015
6.7.2
Setting the response values via channel number
Writing to FTC470XDP (= output of the PROFIBUS Master)
Function
Devices
Channel
No.
BMS
comma
nd
Data
Type
Data
Value
Response value, residual current in mA,
range: 1…20000 mA
RCMS….
1… 12
28
55
value
Response value, residual current in A,
range: 10…2250 A
RCMS….
1… 12
28
56
"
Response value insulation monitoring in k
Ω
IRDH..
1, 2
28
61
"
Prewarning in %
RCMS….
13
28
66
"
Set the digital input to 0 V (low)
MK2418..-11
1… 8
28
70
0
Set the digital input to 24 V (high)
MK2418..-11
1… 8
28
70
1
Relay mode of operation:
0 = N/O operation "N.O." test
1 = N/C operation "N.C." test
2 = Flash 3 = N.O. 4 = N.C.
IRDH..
3, 4
28
81
value
Mode current output:
0 = 0…20 mA 1 = 4…20 mA
IRDH..
5
28
82
"
Mode coupling units:
0 = none 1 = AGH204 AK80 2 = AGH520S
3 = AGH204 AK160 4 = AGH150 AK160
IRDH..
6
28
83
"
Max. leakage capacitance ISOMETER:
0 = 1 μF 1 = 10 μF 2 = 150 μF 3 = 500 μF
IRDH..
7
28
84
"
Repeating self test:
0 = 24 h 1 = 1 h 2 = off
IRDH..
8
28
85
"
Display language:
0 = de 1 = en
IRDH..,
MK2418..
9
28
86
"
Service password:
000…999
IRDH..
10
28
87
"
Function password:
0 = off 1 = on
IRDH..
11
28
88
"
Fault memory:
0 = off 1 = on
IRDH..
12
28
89
"
Start time self test:
00:00…23:59
IRDH..
13
28
90
"
EDS mode:
0 = off 1 = on 2 = auto 3 = 1 cycle
4 = position
IRDH..
14
28
91
"
EDS operation,
system: 0 = DC 1 = AC 2 = 3AC
IRDH..
15
28
92
"
EDS pulse:
0 = 1mA 1 = 2.5 mA 2 = 10 mA
3 = 25 mA 4 = 50 mA
IRDH..
16
28
93
"
EDS position mode:
BMS address setting
IRDH..
17
28
94
"
EDS position mode:
channel no. setting
IRDH..
18
28
95
"
Data value = alarm address x 100 + channel no. (of the
alarm giving device) **
SMO482-12
1… 12
28
96
"
Test address:
0 = all connected devices will be tested
Value = BMS address of the device
MK2418..
13
28
97
"
Buzzer, collective alarm reset:
1 = on 2 = off
MK2418..
14
28
98
"
Personnel:
0 = medical 1 = technical
MK2418..
15
28
99
value