Function
37
FTC470XDP_D00111_00_M_XXEN/02.2015
6.7 Parameterization
6.7.1
Requesting the response values via channel number
Writing to FTC470XDP (= output of the PROFIBUS Master):
Table 6.15: Master request: requesting the device response values
Reading from FTC470XDP (= input data of the PROFIBUS Master)
When the FTC470XDP works in the BMS Slave mode, a temporary Master takeo-
ver is required before carrying out the parameterization below!
Take into consideration that the Master function must be returned by the
FTC470XDP after Master function transfer and the parameterization.
Function
Devices
Channel
No.
BMS
comma
nd
Data
Type
Data
Value
Request for the response value of a device via channel
number
all
channel
No.
30
0
0
Response value, insulation fault location in mA
EDS470
1… 12
30
51
value
Response value, insulation fault location in
μ
A
EDS473, 474
1… 12
30
52
"
Response value of the residual current (mA), range:
1…1000 mA
RCMS….
1… 12
30
55
"
Response value of the residual current (A),
range: 10…2250 A
RCMS….
1… 12
30
56
"
Response value insulation monitoring in k
Ω
IRDH..
1, 2
30
61
"
Set prewarning in %
RCMS….
13
30
66
"
Digital input is set to 0 V (low)
MK2418..-11
1… 8
30
70
0
Digital input is set to 24 V (high)
MK2418..-11
1… 8
30
70
1
Relay mode of operation:
0 = N/O operation "N.O." test
1 = N/C operation "N.C. test
2 = Flash 3 = N.O. 4 = N.C.
IRDH..
3, 4
30
81
value
Mode current output:
0 = 0…20 mA; 1 = 4…20 mA
IRDH..
5
30
82
"
Mode coupling unit:
0 = none 1 = AGH204 AK80 2 = AGH520S
3 = AGH204 AK160 4 = AGH150 AK160
IRDH..
6
30
83
"
Max. leakage capacitance ISOMETER:
0 = 1 μF 1 = 10 μF 2 = 150 μF 3 = 500 μF
IRDH..
7
30
84
"
Repeating self test:
0 = 24 h 1 = 1 h 2 = off
IRDH..
8
30
85
"
Display language:
0 = de 1 = en
IRDH..,
MK2418..
9
30
86
"
Service password:
000…999
IRDH..
10
30
87
"
Function password:
0 = off 1 = on
IRDH..
11
30
88
value
Fault memory:
0 = off 1 = on
IRDH..
12
30
89
value
Start time self test: 00:00…23:59
IRDH..
13
30
90