Function
32
FTC470XDP_D00111_00_M_XXEN/02.2015
Table 6.4: FTC reply to: requests for alarm messages or information about channel number
6.4 Requesting operating messages
Operating messages are measuring values and/or information which is constantly provided by BMS
devices and that can be requested from the BMS Master via the bus. Some BMS devices (EDS47x) do
not provide operating messages, they only provide alarm messages.
6.4.1
Number of all operating messages of a BMS device
Writing to FTC470XDP (= output data of the PROFIBUS Master)
Table 6.5: Master request: number of operating messages
Reading from FTC470XDP (= input data of the PROFIBUS Master)
Table 6.6: FTC answer to: number of operating messages
Function
Devices
Channel
No.
BMS
command
Data
Type
Data
Value
Undervoltage < as value in V
IZ427
4
2
76
value
Voltage in 1/10 V
ATiCS
1, 2
2
87
value
Impedance in k
Ω
IZ427
1
2
91
value
Impedance < as value in k
Ω
IZ427
1
2
92
value
Impedance > as value in k
Ω
IZ427
1
2
93
value
Prewarning Impedance in k
Ω
IZ427
1
2
94
value
This and the following channel numbers are not
available for this device
all
channel
number
2
254
0
Function
Devices
Channel
No.
BMS
command
Data
Type
Data
Value
Requesting the actual number of operating messages
All
0
3
0
0
No operating messages
All
0
3
1
0
Number of operating messages
All
0
3
1
value
Number of operating messages. The alarms
occurred by activating the menu "Test"."
107TD47
IRDH…
PRC487
0
3
3
value
Number of operating messages, occurred during a
test initiated via the interface.
107TD47
IRDH…
0
3
4
value
No device with such an address available.
All
0
3
0
0
Содержание FTC470XDP
Страница 10: ...Safety instructions 10 FTC470XDP_D00111_00_M_XXEN 02 2015...
Страница 22: ...The FTC470XDP protocol converter 22 FTC470XDP_D00111_00_M_XXEN 02 2015...
Страница 26: ...Installation 26 FTC470XDP_D00111_00_M_XXEN 02 2015...
Страница 79: ......