The FTC470XDP protocol converter
20
FTC470XDP_D00111_00_M_XXEN/02.2015
Format of input data:
Byte 1:
Consecutive ID No. of transmission. The ID number corresponds to the associated request (out-
put data).
Byte 2:
No function, the device reads always zero (0) here.
Byte 3:
BMS address of the addressed device. Address corresponds to the associated request (output
data).
Byte 4:
BMS channel number of the addressed device. Channel number corresponds to the associated
request (output data).
Byte 5:
BMS command code, refer to the tables on page 28. Command code corresponds to the associ-
ated request (output data).
Byte 6:
BMS data type, refer to the tables on page 28. The data type represents the requested result
read out by the device.
Byte 7:
BMS high byte data value, refer to the tables on page 28. The data value represents the
requested result read out by the device.
Byte 8:
BMS low byte data value, refer to the tables on page 28. The data value represents the
requested result read out by the device.
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
Consecutive
ID number of
transmission
always
"0"
BMS address of
the addressed
device
Channel number
of the addressed
device
Com-
mand
Type of data
value
High byte
data value
Low byte
data value