Operation
42
6.4.2
Menu 2: History
The non-volatile history memory saves up to 300 data records (alarms,
device errors). If the history memory is full, the oldest entry will be de-
leted in the event of an alarm to create space for the new entry. For de-
tails about erasing the entire history memory refer to chapter "6.4.3.4
Settings menu 4: History".
Line 1:
Event number (if applicable): TEST.
Line 2:
Event start: Date/time
Line 3:
Event acknowledgement (e.g. alarm deleted at IRDH575,
MK800, MK2430, FTC470...):
Date / time
Line 4:
Event end: Date/time
1. If you are searching for an event that occurred at a specific time, use
the arrow keys to scroll to the required entry.
2. Use the "
↵
" key to call up details about the current history memory entry.
Line 1:
Data record number
Line 2:
Alarm/device error designation.
Line 3:
Minimum and maximum measured value
Line 4:
Address and measuring channel of device sending the
message
History no. 297
Start:
21.11.2005 / 15:57:00
Quit:
End:
21.11.2005 / 16:07:03
History no. 297
Insulation fault
Min.
2mA/
Max.
50mA
Addr.:2 Channel:1