COMTRAXX® CP305 - Control Panel
12.2
Relay 1-2 (CP305-IO only)
Menu > Settings > Relay
Carry out operating principle and function for relays 1…2.
Operating principle
Function
Alarm addresses
Buzzer
Alarm addresses | Buzzer
Normally open /
Normally closed
Test Isometer
•
Alarm addresses: Relay responds to each alarm address created. This is independent of
whether the relay has been individually parameterised in the alarm addresses.
•
Buzzer: The relay switches as soon as the buzzer sounds. In this way, other signalling
devices can be installed to indicate pending messages on the CP305.
•
Alarm addresses | Buzzer: Relay switches when either an alarm address or the buzzer is
active.
•
Test Isometer: (relay switches for approx. 30 seconds when a test of the assigned devices
(insulation monitoring devices, LIM, GFCI) is triggered using the “TEST” button).
12.3
Interface
Menu > Settings > Interface
The parameters required for each connected interface are set here:
Ethernet
Make Ethernet settings. The parameterised IP address is displayed.
If DHCP is switched off, the IP address must be set manually.
BMS
Address (1…90)
Interval (1…3 s)
Acknowledgement via interface (on, off )
CP305_D00425_00_M_XXEN_09.2022
51