28 CC612(4G)_D00325_06_M_XXEN/09.2021
Configuration and testing
5.1.2 Remote configuration of parameters
The charging system or charging system controller enables the configuration of many parameters using the
OCPP GetConfiguration and ChangeConfiguration commands. With these commands, locally configured com-
munication parameters can be changed. The exception is the SIM parameters, which require local interven-
tion when the SIM card is replaced.
i
Any backend system can be used.
5.1.3 Factory settings
i
Resetting to factory settings deletes all settings except the serial number.
Click the
"Operator Default & Restart"
button
on the
Operator
tab to reset changed parame-
ters of the operator configuration to default.
Click the
"Settings Default & Restart
" button
on the
Settings
tab to reset changed parame-
ters to default.
Click the
"Manufacturer Default & Restart"
button on the
Manufacturer
tab to reset changed parameters of
the manufacturer configuration to default.
Click the
"Factory Reset & Restart"
button to reset the charge controller to factory settings.
5.1.4 Testing
After completing the configuration, the charge controller must be tested for operability. The following is
checked:
• Successful boot process
• If intended, establishment of backend connection
• Connection to meter possible
• Plug locking and unlocking works.
• Charging is possible
5.1.5 Successful boot-up
The boot-up process begins once 12 V is supplied to the charge controller. After about 30 s, the ALARM and
READY LEDs - and the PLC LED when available - on the front panel light up. After some time, the LEDs are tur-
ned off and only the „READY“ LED blinks, indicating a successful boot-up. At the same time, the „Free LED“ on
the RFID module (if configured) lights continuously, marking the end of the boot up sequence
5.1.6 Connectivity to the backend
5.1.6.1 Connection of the charge controller to the backend
Go to the
Settings
tab (http://192.168.123.123/operator/settings). To access this tab, enter the following user
name and password:
• User name: operator
• Password: yellow_zone