Alarm/ meas. values
A detailed query of the values can be found at
Menu: 1. Alarm/meas. values
(select menu
item
) for detailed information about the values. Select the individual entries by
means of the
buttons.
For each of these entries you can check whether an alarm exists or not:
= no alarm
= alarm
•
* Measuring channel 11
: The text depends on the existing messages. If several messages
exist, individual messages are indicated alternately on the display every four seconds.
•
* Measuring channel 16
: Indicates the total time passed during the self test from simulat-
ing 0 V on L1 to
disconnecting
interface switch 1. (Refer to "Manual self test" on
•
* Measuring channel 17
: Indicates the total time passed during the self test from simulat-
ing 0 V on L1 to the
disconnection command
for interface switch 1. (Refer to "Manual
Measuring
channel
Parameter
VALUE
1
U
(1-N)
:
2
U
(2-N)
:
3
U
(3-N)
:
4
U10LN:
5
U10LL:
6
U
(1-2)
:
7
U
(2-3)
:
8
U
(3-1)
:
9
Frequency:
10
df/dt:
11
Contact moni-
tor. K1*
12
t
(ON)
:
13
Unbalance:
14
Vect.shift:
15
Phase
sequence:
4501_2
16
t
(OFF) TOT
*:
16
t
(OFF)
K1 **
17
t
(OFF) DEVICE
*
17
t
(OFF)
K2 **