Installation, connection and commissioning
30
VMD460-NA_D00001_05_M_XXEN/01.2020
4.8.3
VDE-AR-N 4110:2018-11 – basic program 4110
Application/Use: higher-level decoupling protection of the generating plant without
QU protection in the context of VDE-AR-N 4110:2019-11.
Automatic reconnection is not permitted after a disconnection due to a tripped protec-
tive or monitoring function of the generating plant. Reconnection may only take place
after approval by the network control centre.
(VDE-AR-N 4110:2018-11 chapter 10.4.2 par. 1)
In order to meet this requirement with the VDM460-NA, the use of the remote trip func-
tion (remote disconnection) in conjunction with an external circuit must be implement-
ed. The following wiring diagram and the corresponding explanation is only one
possible example:
K2
24
22
21
K1
14
12
11
L1
L2
L3
N
6 A
6 A
6 A
A2
6 A
A1
6 A
U
S
D2
DG1/2
D1
L1
L2
L3
N
K3
K4
RE
VMD460
V
LINETRAXX®
A
B
RTG
RT1
D4
D3
DG3/4
11
12
14
21
22
24
L3
L2
L1
D2
D1
DG1/2
D4
N
D3
RTG
RT1
DG3/4
ESC
1
2
3
4
5
6
7
Interface switch 1
Interface switch 2
Generating
plant
8
9
10