Installation, connection and commissioning
17
COM461MT_D00011_00_M_XXEN/05.2013
4.4
Connecting the device
For UL applications, the following is to be observed:
– Supply voltage
U
s
see nameplate and ordering data
– Maximum ambient temperature 55°C
– For use in pollution degree 2 environments
– Only 60/75 °C copper wires are to be used
– Tightening torque for terminals 0.5…0.6 Nm
Connect the terminals and sockets on the COM461MT according to the wiring
diagram.
BMS-Bus
RS-485
A2
A1
ETH1 ETH2
A1 A2
A B
2 x RJ45
6 A
6 A
U
S