72
ATICS-2-ISO_D00046_04_M_XXEN / 03.2021
Menu mode: Operation and setting
Menu
Description
7. t(off)
Delay on release load:
Setting range:
0 s…100 s
Resolution of setting: 1 s
8. Temperature
on
Temperature monitoring enabled
off
Temperature monitoring disabled
9. Fault location
off
Insulation fault location disabled
auto
Insulation fault location enabled
Note: This function is only available if a suitable master is
connected via the BMS bus (e.g. MK2430, TM800, CP9xx,
COM465…).
10. IT system
230
Nominal voltage of the IT system being monitored: 230 V
115
Nominal voltage of the IT system being monitored: 115 V
7.3.4.5 Settings menu 5: Relay
In this menu, you can adjust settings for the mode of operation and function of the relay output (alarm
relay) of the ATICS-2-ISO. The function can be set for the relay as follows: Alarm message, "Active",
Generator Start.
If "Alarm" is set and then "Line 1: on" is selected, the relay switches if line 1 fails. If "Active" is set and
then "Line 1: on" is selected, the relay switches if line 1 operating. The setting "on" can be selected for
several menus simultaneously. The relay switches when at least one of the conditions is met.
If a new alarm appears while another is already pending, the relay is deenergised briefly (approx. 1s)
and is energised again. This "new value behaviour" ensures that new alarms are reported when alarm
messages are forwarded to SCADA systems.
If "GenSt" is set, the operating mode for the alarm relay will always be set to "N/C-T" on. The other set-
tings on the "Relay" menu are disabled. The alarm message "Failure line 2" is suppressed.
i
If the setting "Line G" is selected in the "Changeover -> System" settings menu, the alarm relay is per-
manently set to:
- 1. Function:
GenSt
- 2. Relay mode:
N/C-T
- Menu items 4…12
inactive
Содержание ATICS-2-63A-ISO
Страница 10: ...10 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 Intended use...
Страница 12: ...12 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 System description...
Страница 21: ...ATICS 2 ISO_D00046_04_M_XXEN 03 2021 21 ATICS 2 63A ISO...
Страница 41: ...ATICS 2 ISO_D00046_04_M_XXEN 03 2021 41 ATICS 2 63A ISO...
Страница 82: ...82 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 Troubleshooting...
Страница 100: ...100 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 Technical data 10 2 T V test report according to VDE 0100 Part 710...
Страница 101: ...ATICS 2 ISO_D00046_04_M_XXEN 03 2021 101 ATICS 2 63A ISO 10 3 T V certificate regarding functional safety...