ATICS-2-ISO_D00046_04_M_XXEN / 03.2021 69
ATICS-2-63A-ISO
Menu item
Function
9. Reminder
Prewarning time for test interval (set value smaller than test interval):
Setting range:
off, 1…60 days
Resolution of setting: 1 day
10. Serviceinterv.
Service interval:
Setting range:
off, 6…48 months
Resolution of setting: 6 months
11. Reminder
Warning time for service interval (d=day):
Setting range:
off, 1…60 days
Resolution of setting: 1 day
12. t (GenStart)
Time delay for changeover to generator (measured from "Voltage
line 2 = OK"):
Setting range:
0 s…100 s (only active when System=Line G)
Resolution of settings: 1 s / 5 s
13. t(GenMax)
Maximum generator start time. Monitoring whether the generator starts (time until
"Voltage line 2 = OK").
Setting range:
0 s…100 s (only active when System=Line G)
Resolution of setting: 1 s / 5 s
14. t(Gen.off)
Time delay for turning off the generator after switching back to
the preferred line:
Setting range:
2 s…180 min (only active when System=Line G)
Resolution of setting: 1 s / 5 s / 1 min
15. Load disconn.*
on:
Operation with ATICS-ES; device switches to position 0 if both
lines
fail.
off:
Device remains in the last switch position if both lines fail.
* only for "-ES" version of ATICS®
7.3.4.2 Settings menu 2: Voltage
In this menu you can make settings for voltage monitoring on line 1 and line 2 individually or together.
Example:
Line 1 is set to "Undervolt: 184 V". If the voltage on line 1 falls below 184 V, the device dis-
plays an alarm message. If the voltage on line 2 is within the set range, a changeover to line 2 takes
place. The ATICS® returns to line 1 if the voltage on line 1 exceeds the pre-set value (in this case 184 V)
plus the set hysteresis.
Содержание ATICS-2-63A-ISO
Страница 10: ...10 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 Intended use...
Страница 12: ...12 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 System description...
Страница 21: ...ATICS 2 ISO_D00046_04_M_XXEN 03 2021 21 ATICS 2 63A ISO...
Страница 41: ...ATICS 2 ISO_D00046_04_M_XXEN 03 2021 41 ATICS 2 63A ISO...
Страница 82: ...82 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 Troubleshooting...
Страница 100: ...100 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 Technical data 10 2 T V test report according to VDE 0100 Part 710...
Страница 101: ...ATICS 2 ISO_D00046_04_M_XXEN 03 2021 101 ATICS 2 63A ISO 10 3 T V certificate regarding functional safety...