Menu mode: Operation and setting
70
ATICS-DIO_D00080_01_M_XXEN/04.2015
7.3.4.3
Settings menu 3: Current
On this menu, you can adjust settings for current monitoring (short-circuit detection) downstream
of the transfer switching device.
Settings menu 3: Current for ATICS-2-DIO
The current is detected via a measuring current transformer (T3 in the connection example).
Settings menu 3: Current for ATICS-4-DIO
The current is detected via the measuring current transformers (T3…T6 in the connection example).
If the optional measuring current transformer T6 is not available, its function has to be switched off
in the "Current 4" menu. Choose a measuring current transformer:
1. Use the arrow button "
" to set the measuring current transformer. Press "
↵
".
2. Use the arrow buttons to select a measuring current transformer (e.g. Current 2) or all the four
measuring current transformers (Current 1…4). Press "
↵
" to confirm your selection.
Menu
Meaning
Exit
Exit settings menu "Current"; go up one menu level
1. Mode
on
Current monitoring is switched on
off
No current monitoring
2. CT
STW3
Bender measuring current transformer STW3
STW4
Bender measuring current transformer STW4
3. CT monitor.
on
Transformer monitoring is switched on
off
Transformer monitoring switched off
Note:
External interference from loads can cause false trippings. In this case, the
function has to be deactivated.
Menu
Meaning
Exit
Exit settings menu "Current"; go up one menu level
1. Mode
on
Current monitoring is switched on
off
Current monitoring switched off
2. CT
STW3
Bender measuring current transformer STW3
STW4
Bender measuring current transformer STW4
3. CT monitor.
on
Transformer monitoring is switched on
off
Transformer monitoring switched off
Note:
External interference from loads can cause false trippings. In this case, the
function has to be deactivated.
Current: 2
Exit
1.Mode: on
2.CT: STW3
Current: 1..4
Exit
1.Mode: on
2.CT: STW3
Setting a measuring
current transformer
Setting all four measuring
current transformers
Содержание ATICS-2-63A-DIO
Страница 22: ...System description 22 ATICS DIO_D00080_01_M_XXEN 04 2015...
Страница 44: ...Commissioning settings and testing 44 ATICS DIO_D00080_01_M_XXEN 04 2015...
Страница 58: ...Operation 58 ATICS DIO_D00080_01_M_XXEN 04 2015...
Страница 86: ...Troubleshooting 86 ATICS DIO_D00080_01_M_XXEN 04 2015...
Страница 95: ...95 ATICS DIO_D00080_01_M_XXEN 04 2015 10 Data 10 1 T V test report...
Страница 102: ...Data 102 ATICS DIO_D00080_01_M_XXEN 04 2015...