Operation
57
ATICS-DIO_D00080_01_M_XXEN/04.2015
6.2.5.3
Reset menu 3: Changeover
ATICS® monitors the parameters important for its service life. On reaching the set limits, the unit dis-
plays an alarm message. Replacement of the device must be initiated. During the period until it is re-
placed the annoying alarm can be "deleted" by increasing the limits.
* for functional safety
Delete
Set new alarm value. Cancel alarm.
Cancel
Back to reset menu
Once the stipulated service life has been exceeded, safe operation of the
transfer switching device is not guaranteed!
Fatigued components can fail. Replace the device as soon as possible.
Menu
Meaning
Exit
Exit "Changeover" reset menu; go up one menu level
1.
Changeover: xxx
Number of changeovers performed
2. Alarm:
8000
Alarm value for maximum number of changeovers performed*
Delete
Increase alarm value by 500 changeovers
4.
Operat. time: xxh
Operating hours counter (h=hours, d=days, mo=months)
5. Alarm:
120mo
Alarm value for maximum number of operating hours*
Delete
Increase value by 200 days (this is only possible when the alarm value is
already exceeded)
7.
Changeover I>: 0
Number of changeovers performed which were carried out with overcurrent
or short-circuit current (see also "Menu 2: Changeover" on page 63)
8. Alarm:
1
Alarm value for maximum permitted number of changeovers performed
which were carried out with overcurrent or short-circuit current*
Delete
Increase alarm value by 1 changeover
WARNING
Delete
Cancel
Delete
Содержание ATICS-2-63A-DIO
Страница 22: ...System description 22 ATICS DIO_D00080_01_M_XXEN 04 2015...
Страница 44: ...Commissioning settings and testing 44 ATICS DIO_D00080_01_M_XXEN 04 2015...
Страница 58: ...Operation 58 ATICS DIO_D00080_01_M_XXEN 04 2015...
Страница 86: ...Troubleshooting 86 ATICS DIO_D00080_01_M_XXEN 04 2015...
Страница 95: ...95 ATICS DIO_D00080_01_M_XXEN 04 2015 10 Data 10 1 T V test report...
Страница 102: ...Data 102 ATICS DIO_D00080_01_M_XXEN 04 2015...