System description
18
ATICS-DIO_D00080_01_M_XXEN/04.2015
3.5.1.3
Time diagram: Changeover to generator mode
T(Imp)
: Pulse time: 15 … 30 m
s
T(0)
: Dead time
T(on)
1
: Response delay ALARM failure voltage Line 1
T(off)
1
: Delay on release ALARM
fa
ilur
e
voltage
L
in
e
1
T(2->1)
: Return transfer delay time
: + Measuring time: approx. 50 ms
: + Measuring time: approx. 50
ms
Voltage
Line 1
Switch
position
Voltage
output
ATICS
Voltage
Line 2
Time
delay
1
0
2
T(on)
1
T(Imp)
T(0)
T(I
m
p
)
T(
off
)
1
T(
Im
p)
T(0)
T(
Imp)
Generator mode
Switching back to Line 1 (normal operation
with delay on release)
10
0
2
1
T(2->
1
)
Alarm failure
Line 1
Alarm failure
Line 2
Generator
start relay
T(GenStar)
: Generator start-up delay, delayed changeover to generator.
Measurements beyond "Voltage Line 2" ok.
T(
Ge
n
Start)
T(GenOff)
: Generator disconnecting delay time, delayed switching-off of the generator.
T(GenOff)
T(
GenMax)
T(GenMax)
: Generator start-up time. Monitoring the generator start-up.
Not
e:
Ti
mes are not shown to
scale.
Содержание ATICS-2-63A-DIO
Страница 22: ...System description 22 ATICS DIO_D00080_01_M_XXEN 04 2015...
Страница 44: ...Commissioning settings and testing 44 ATICS DIO_D00080_01_M_XXEN 04 2015...
Страница 58: ...Operation 58 ATICS DIO_D00080_01_M_XXEN 04 2015...
Страница 86: ...Troubleshooting 86 ATICS DIO_D00080_01_M_XXEN 04 2015...
Страница 95: ...95 ATICS DIO_D00080_01_M_XXEN 04 2015 10 Data 10 1 T V test report...
Страница 102: ...Data 102 ATICS DIO_D00080_01_M_XXEN 04 2015...