3. Function
3.1
Device characteristics
Monitoring for DC charging stations (mode 4 acc. to IEC 61851-23) for
charging of electric vehicles
Measurement of the nominal system voltage
U
n
(True RMS) with und-
ervoltage and overvoltage detection
Measurement of residual voltages system to earth (L+/PE and L-/PE)
Automatic adaptation to the system leakage capacitance
C
e
up to 5 μF
or 20 μF
Automatic device self test with connection monitoring
Selectable start-up delay, response delay and delay on release
Two separately adjustable response value ranges of 1kΩ …500 kΩ
(Alarm 1, Alarm 2)
Alarm signalling via LEDs ("AL1", "AL2"), a display and alarm relays ("K1",
"K2")
N/C operation or N/O operation of the relays selectable
Measured value indication via multi-functional LCD
Fault memory can be activated
RS-485 (galvanically isolated) including the following protocols:
– BMS interface (Bender measuring device interface) for data
exchange with other Bender components
– Modbus RTU
– IsoData (for continuous data output)
Password protection to prevent unauthorised parameter changes