background image

Page 28

Page 29

BOILERMA

TE 

2000

When commissioning the system

•      If the boiler is range rated, then adjust it to the 

maximum

 heat input.

     Check the boiler thermostat is set to maximum.

•    

Set  the  boiler  pump  speed  so  that  the  temperature  difference  across  the 

       boiler  is 

about  8°C

  -  when  the  space  heating  is  off. 

  NOTE

:    For  optimum 

       performance  when  using  a  condensing  boiler  such  as  the  Keston  C25  set 
       the boiler pump in the BoilerMate to give about 15ºC temperature rise across 
       the boiler.

•    

Set the heating system pump speed so that the temperature difference across 

       the flow and return 

is not greater than 11°C.

•      Check the DHW plate heat exchanger pump is set to maximum.
•      Check  that  there  is  no  overflow  when  the  whole  of  the  system  is  fully  up 
       to temperature.
•      Check  that  the Y type strainer on the incoming mains cold water inlet to the 
       appliance is clean.

Note

:  If the appliance is operating at mains cold water pressures below 11⁄2 bar the 

flow regulator fitted on the outlet to the Y type strainer can be removed if required 
to improve performance.
        

 

 

Because the A.C.B is able to adjust to suit the 
water temperatures delivered by the boiler the 
thermostat should always be set at maximum 
during commissioning.

However, the boiler thermostat setting can be 
reduced in summer, in the normal way, if the 
appliance is being used for hot water only.

The  temperature  settings  established  during 
commissioning    can  be  checked  using  push 
button  switches  sw1  and  sw2  on  the  PCB  as 
described in section 3.3 Fault Finding.

The  clock/programmer  provided  on  the 
appliance  controls  the  heating  system  only 
and  should  be  set  to  suit  the  householders 
requirements  using  the  instructions  shown 
on  the  separate  leaflet  and  the  label  on  the 
front of the appliance.  If the appliance is fitted 
with Switch (see figure on page 25) the boiler 
should  be  switched  off  and  Switch  operated 
to ensure it is working correctly.

•      When  the  selector  knob  is  not  in  normal 
       position,  the  PCB,  room  thermostat  and 
       the time clock are electrically isolated.

•      When  the  selector  knob  is  in  HW  only 
       position  the  plate  heat  exchanger  pump 
       will run continuously at full speed.

•      When the selector knob is in the HW and 
       HTG  position,  the  plate  heat  exchanger 
       pump  and  the  heating  pump  will  run 
       continuously.

This product is covered by the ‘Benchmark’ 
scheme  and  a  separate  commissioning/
service  log  book  is  included  with  this 
product.   This  must  be  completed  during 
commissioning  and  left  with  the  product 
to  meet  the Warranty  conditions  offered 
by Gledhill.

On completion:- 

1.    Do  ensure  that  the  electrical  connection 
       (e.g.  mains  supply,  room  thermostat)  to 
       the  unit  is  correct  and  tight  before 
       starting the commissioning procedure.    

2.    Do  ensure  that  the  functioning  and 
       control  of  the  system  is  explained  to  the 
       occupant.       

These Instructions should be placed along with 
the component manufacturers instructions in the 
pocket provided on the rear of the front panel.  
The front panel should then be refitted.

2.3 COMMISSIONING

2.0  INSTALLATION

Note: 

The controls within the A.C.B will not allow the heating system to function 

until the store temperature has reached 60°C.   Therefore although the LED bar 1 
‘HT’ will light when heating is switched on, the heating pump (Green LED -3) will not 
switch on if the store temperature is less than 60°C. Time will need to be allowed for 
this to happen during initial commissioning.  This will vary depending on the boiler 
size and the model of the BoilerMate 2000 being used. 

2.    Once a temperature of 60°C has been reached on the thermal store, switch on 
       space heating clock/programmer and room thermostat.

•    

Horizontal LED bar 1 ‘HT’ will light.

•    

Green LED 3 on the A.C.B will switch  on.

       Heating pump will run.

3.    Switch off space heating on clock/programmer or room thermostat

•    

Horizontal LED bar 1 ‘HT’ will switch off.

•    

Green LED 3 on the A.C.B will switch off.

       Heating pump will switch off.

4.    Open the hot tap 

•    

Horizontal LED bar 3 ‘HW’ on the LED display will light.

•    

Domestic hot water pump will run.

5.    Close the hot water tap

•    

Horizontal LED bar 3 will switch off

•    

Domestic hot water pump will continue to run for a short period of time before 

       switching off. 

6.    The  A.C.B  incorporates  a  3  minute  pump  overrun  facility.    Check  green  LED 
       2  remains  lit  for  this  period  of  time  when  the  boiler  switches  off  i.e.  the 
       thermal store reaches temperature. 

The control functions have now been checked. 
Let the boiler heat the store and when the store is satisfied, i.e. green LED’s 1 and 2 
on the A.C.B are off, the radiator circuit and hot water can be checked and balanced 
in the normal way.
The  boiler  thermostat  should  be  left 

at  maximum

  for  optimum  performance/

efficiency.

Содержание Gledhill BoilerMate 2000 125

Страница 1: ...MAINS PRESSURE HOT WATER SUPPLY SYSTEM INCORPORATING A THERMAL STORE ALL MODELS COMPLY WITH THE WATER HEATER MANUFACTURERS SPECIFICATION FOR INTEGRATED THERMAL STORES BOILERMATE 2000 BOILERMATE 2000 G...

Страница 2: ...ity System audited by BSI Patents Pending TheGledhillGroup sfirstpriorityistogivea high quality service to our customers Quality is built into every Gledhill product and we hope you get satisfactory s...

Страница 3: ...BoilerMate 2000 is not covered by section G3 of the current Building Regulations and is therefore not notifiable to Building Control The information in this manual is provided to assist generally in...

Страница 4: ...The outlet temperature of the domestic hot water is maintained by a printed circuit board which controls the speed of the pump circulating the primary water from the store through the plate heat exch...

Страница 5: ...e d o M 5 2 1 M B 5 4 1 M B 5 8 1 M B 0 1 2 M B 5 2 2 M B y t p m e t h g i e W g k 8 5 g k 1 6 g k 5 6 g k 6 7 g k 8 8 l l u f t h g i e W g k 3 7 1 g k 6 8 1 g k 5 1 2 g k 6 4 2 g k 8 7 2 p m u P W...

Страница 6: ...ion cistern complete with ballvalve overflow fitting and cold feed open vent pipework assembly is supplied separately Optional Equipment A soft water model is available for areas where the hardness le...

Страница 7: ...O I S N E M I D E C N A I L P P A l e d o M t h g i e H h t d i W h t p e D A B C 5 2 1 M B m m 0 4 1 1 m m 5 9 5 m m 5 9 5 5 4 1 M B m m 0 4 1 1 m m 5 9 5 m m 5 9 5 5 8 1 M B m m 0 5 3 1 m m 5 9 5 m...

Страница 8: ...Page 8 1 0 DESIGN 1 2 TECHNICAL DATA...

Страница 9: ...BOILERMATE 2000 1 2 TECHNICAL DATA AWAITING HOT WATER PERFORMANCE GRAPHS FOR EACH MODEL SIZE PERFORMANCE GRAPHS OF GRUNDFOS PUMPS 1 0 DESIGN GRUNDFOS 15 50 litres sec 6 litres sec GRUNDFOS 15 60 TO BE...

Страница 10: ...optional extra are being used or if all taps are provided with flow regulators the flow regulator on the cold inlet should be removed No check valve or similar device should be fitted on the cold wat...

Страница 11: ...ed fully in accordance with their recommendations This is particularly important in relation to use of push fit connections when using the optional flexible hose kits see 2 2 Installation Pipework con...

Страница 12: ...vity circulation does not occur when the heating pump is not running To be certain of preventing this it is recommended that a check valve or valves are fitted on the vertical flow pipes Thewaterlevel...

Страница 13: ...ework systems can be used in place of copper internally as long as the chosen system is recommended for use on domestic heating systems by the manufacturer and is installed fully in accordance with th...

Страница 14: ...erMate 2000 and the boiler during dormant periods An automatic air vent will be required on the flow adjacent to the boiler and depending upon the pipe layout a manual air vent may also be required on...

Страница 15: ...lockshield valves on the radiators If this is not done the performance of the BoilerMate will be adversely affected If heating of a single bathroom radiator or towel rail is required in summer then it...

Страница 16: ...e system that has been installed If the primary pipework dips or the boiler is located above the BoilerMate a single F E cistern with a cold feed and open vent piped to the cistern should be used This...

Страница 17: ...heating modes In the former only hot water pump and electric heating element are energized In the latter the heating system pump is also energized This means that the heating will be on permanently u...

Страница 18: ...mperatures will normally be higher than in a conventional system and the design of the cupboard and door will need to take this into account No ventilationisnormallyrequiredtothecupboard A suitable lo...

Страница 19: ...ecommended method is shown opposite Before installation the site requirements should be checked and confirmed as acceptable The plastic cover and protective wrapping should be removed from the applian...

Страница 20: ...on fittings Connection E is blanked 15mm copper pipe Connection J is RC1 2 1 2 in BSPT internal A Safety open vent B Cold feed expansion C Primary flow from boiler D Primary return to boiler E Towel r...

Страница 21: ...F E cistern and pipework site run by the installer to connect this to the appliance Obviously any pipework in the roof space and the feed and expansion cistern will need to be adequately insulated to...

Страница 22: ...age 22 WIRING DIAGRAM STANDARD BOILERMATE 2000 APPLIANCE 2 0 INSTALLATION 2 2 INSTALLATION Y E K L B E U L B R B N W O R B Y G W O L L E Y N E E R G R D E R K L B K C A L B Y W O L L E Y H W E T I H W...

Страница 23: ...from an earthing strap on the primary return to boiler pipe to the earth stud on the wiring panel 2 0 INSTALLATION Make the connections as shown opposite on the terminal strip provided The appliance...

Страница 24: ...Frost Protection When frost protection is required for the whole house or where a base temperature is required during cold weather then a frost thermostat should be wired across plug in terminals 21 a...

Страница 25: ...Page 25 BOILERMATE 2000 2 0 INSTALLATION 2 2 INSTALLATION WIRING DIAGRAM BOILERMATE2000 WITH SWITCH...

Страница 26: ...e service slot provided in the base of appliance The recommendations contained under Electrical Connection Standard Appliance should be followed when connecting a remote clock room thermostat boiler e...

Страница 27: ...n Check the water level in the feed and expansion cistern and adjust the ballvalve if necessary Check the whole of the primary heating and domestic hot and cold distribution systems for leaks It is es...

Страница 28: ...MAXIMUM 2 Switch off heating on the clock programmer and room thermostat 3 Switch off hot water on the programmer if 2 channel clock is fitted 4 Check the jumper settings are correct These must all be...

Страница 29: ...heating pump will run continuously This product is covered by the Benchmark scheme and a separate commissioning service log book is included with this product This must be completed during commissioni...

Страница 30: ...T use a BoilerMate on a sealed primary i e closed system 13 DON T use pipe smaller than 28mm between the boiler and the BoilerMate when the boiler rating exceeds 20kW about 68 000 Btu h 14 DON T use d...

Страница 31: ...ts specialist heating spares suppliers Help and advice is also available from the Technical Helpline on 01253 474401 However allcomponentsarereadilyaccessible and can be changed quickly and easily by...

Страница 32: ...a l P p e w S 7 1 0 T G 4 6 6 5 0 E 0 1 B C A d r a o b l o r t n o c e c n a i l p p A k o l E 5 5 2 B X 8 5 1 9 3 E 1 1 r o s n e s e r o t S k o l E 9 4 1 T G 2 2 0 6 2 E 2 1 r o s n e s n r u t e...

Страница 33: ...Page 33 BOILERMATE 2000 3 0 SERVICING...

Страница 34: ...at the space heating and hot water load is not greater than the boiler output and that the BoilerMate 2000 model is suitable for the type of dwelling If all the above checks are satisfactory then it i...

Страница 35: ...tric backup this should be switched on and operated in accordance with the instructions on the label fitted to the appliance until the installer manufacturer can attend When requesting a visit from th...

Страница 36: ...s as in Option 4 for Taps Mixers APPENDIX A WATER SAVINGS OPTIONS FOR SHOWERS 4 FIXING OPTIONS FOR TAPS MIXERS 1 MK Range Combined Regulators Aerator for screwing onto Taps Mixers with internal or ext...

Страница 37: ...d close to the appliance if required 0 5 0 P I M e d o C k c o t S 1 e p y t d l o f i n a M m o o r k a o l c e n o m o o r r e w o h s e t i u s n e e n o m o o r h t a b e n o r o t a l u g e r w o...

Страница 38: ...ework in table 2 r e p p o c m m 5 1 n i h t g n e l e p i p t n e l a v i u q e m u m i x a M 1 e l b a T e r u s s e r p t e l n I r a b m e p i p f o h t n e l t n e l a v i u q e m u m i x a M m l...

Страница 39: ...al connection of fittings to the manifold will need to suit the arrangements shown on page 35 Note 1 If it is proposed to fit chemical water treatment such as a water softener this should be fitted in...

Страница 40: ...he contractors installers reasonable costs in removing and replacing any defective Open Vented Copper Cylinder or Tank with defective integral pipework as follows Gledhill Water Storage Ltd AMD AUGUST...

Страница 41: ...ses owned or occupied by the Purchaser or in the possession of the Purchaser for the purposes of repossessing and recovering any such goods the property in which has remained in us under paragraph 2 a...

Страница 42: ......

Страница 43: ......

Страница 44: ......

Отзывы: