M200+ Software Version 1.4 - 1.5

C200+ Software Version 2.3, PCB Issue 2.1

Master 200Plus - Wardens Call System

Operators Manual

Bell System (Telephones) Ltd

Presley Way, Crownhill, Milton Keynes, MK8 0ET.

Содержание Master 200Plus

Страница 1: ...er 2003 PD001 Iss 2 M200 Software Version 1 4 1 5 C200 Software Version 2 3 PCB Issue 2 1 Master 200Plus Wardens Call System Operators Manual Bell System Telephones Ltd Presley Way Crownhill Milton Keynes MK8 0ET ...

Страница 2: ... 9 Gaining Access to Master or Monitor Mode 9 Converting a Monitor Station into a Master Station 12 Other Monitor Mode Messages 12 Un Mastering Un Monitoring a Unit 13 Diagram 3 Gaining Access to Master or Monitor Mode 14 Receiving Alarm Calls 15 No Activity 15 Alarm Calls Messages 15 Establishing Speech With a Calling Unit 17 Volume Adjustment During Speech 17 Cancelling an Alarm Call Following S...

Страница 3: ... 4 Handling a Typical Alarm 21 Calling a Room Unit 22 Calling Up a Room Unit Numeric Flat Number 22 Calling Up a Room Unit Alpha Numeric Flat Number 23 Calling Up a Room Units with the Same Number 24 Speech Operation 26 Annunciation Tone 26 Privacy Operation 26 Invalid Flat Number 27 Self Diagnostic Messages 28 Power up Reset Message 28 Fault Codes 28 ...

Страница 4: ...18 September 2003 PD001 Iss 2 1 Diagram 1 The M200 Room Unit ...

Страница 5: ...18 September 2003 PD001 Iss 2 2 Diagram 2 System Overview ...

Страница 6: ...ves as a call point from which the residents may make an alarm call using the integral call button pull cord or other external alarm switch device see M200 accessories listed below In addition each Room Unit has a keypad and display for use by the Warden or Nursing staff Any unit may therefore be used to monitor alarm calls to establish speech communication with the residents and to perform variou...

Страница 7: ...he dummy plug supplied or by disabling the feature by programming Smoke Detector A suitable smoke detector may connected to the Smoke Detector input of the room unit A high priority alarm call is generated if the smoke detector is triggered Remote Alarm 2 One or more of these remote switches may be connected to the Room Unit to enable an alarm call to be made from various positions within a flat T...

Страница 8: ... Computer During installation the controller may be connected to an IBM or compatible PC desktop or laptop via an RS232 or RS422 cable in order to program the system with several custom parameters e g the list of valid flat numbers GroupMaster 200 Software This is a Microsoft Windows software package designed to be used with a PC The GroupMaster 200 software enables several extra features that inc...

Страница 9: ...tion where staff can converse with the resident and determine the necessary course of action For further information see the D200 Auto Dialler Installation Operators Manual Door Entry Panel The Door Entry Panel provides a means of connecting a door entrance panel at the building entrance to an M200 Warden Call System For further information see the DEP200 Door Panel Installation Manual GPI200 The ...

Страница 10: ... the resident cannot be listened in to unless they have made an alarm call If the privacy button is pressed during speech the effect is only temporary returning to the previous setting when speech is finished The privacy button has several programmable options i Permanently On the privacy button has no effect except during speech ii Permanently Off the privacy button has no effect iii Default to o...

Страница 11: ...ack socket or by inadvertent removal of the jack plug In each case the M200 room unit will illuminate the Re Assurance Lamp Red LED and illuminated ceiling pull switches if present The staff are alerted to alarms by a Any room unit enabled as a Master Monitor sounding an alarm tone provided the unit is programmed to do so b Extension alarms such as an audible alarm or flashing lamp if present c A ...

Страница 12: ...order to carry out the command Only if the current Master is in use at the time ie locked will this action be inhibited A Master becomes locked whenever speech is in progress and also for a short period of time immediately after the unit was made a Master There is no limit to the number of Monitor units on a system however a maximum of 4 including the Master unit can sound an alarm tone simultaneo...

Страница 13: ... September 2003 PD001 Iss 2 10 Proceed as follows Display Press m ENTER CODE ____ Display Type 1234 ENTER CODE ___ or other access code ENTER CODE __ ENTER CODE _ Display momentarily Waiting for response ...

Страница 14: ...er MASTER Indicates Master access granted Display for 2 seconds Or there is currently a Master station MASTER AT 12A Indicates Master access not granted Unit in Monitor mode Display No Calls Message may vary with circumstances See also Diagram 3 Gaining Access to Master or Monitor Mode ...

Страница 15: ...er will display 12A is the current locked Master station Master at 12a Pressing other function keys such as connect Speech will automatically make a unit a Master unless the current Master is locked in order to carry out that function Other Monitor Mode Messages If an attempt is made to become a Master when either the AllCall amplifier or the central monitoring station is in use one of the followi...

Страница 16: ...red as a Master or Monitor it be returned to RESIDENT MODE Otherwise it may be impossible for the resident to make an alarm call this is done by pressing the ukey It is also possible for a room unit to be programmed to remain in Master Monitor mode for a limited time period Refer to the Installation Manual for details ...

Страница 17: ...18 September 2003 PD001 Iss 2 14 Diagram 3 Gaining Access to Master or Monitor Mode ...

Страница 18: ...splay will show NO CALLS Alarm Calls Messages If there is an alarm call the Master station and Monitor stations will display the flat number as well as the Alarm type as follows Call button or pull cord alarm at flat 2020 ALARM 2020 Remote switch ceiling pull switch alarm at flat ALARM REM 12A 12A Auxiliary switch Jack socket e g Pear Drop ALARM AUX 101 Switch alarm at flat 101 Remote switch alarm...

Страница 19: ...18 September 2003 PD001 Iss 2 16 Remote switch alarm in the bathroom of flat ALARM BATH 57B 57B Smoke detector alarm at flat 10 FIRE ALARM 10 Call for assistance alarm at flat G2 HELP AT G2 ...

Страница 20: ... high SPEECH HI 12A If there are additional alarm calls waiting to be dealt with the flat number and re assurance lamp red LED will flash Volume Adjustment During Speech When a resident makes an alarm call he or she may be positioned close to the room unit or a distance away To allow for this the M200 system has a High and Low volume level for received speech The operator may change the volume lev...

Страница 21: ...ancel the alarm call at source see Local Cancel below The button will only be effective whilst in speech mode it is not possible to cancel an alarm without first connecting the alarm This feature helps to prevent inadvertent cancellation due to operator error Cancelling an Alarm Call from the Calling Unit Local Cancel To cancel an alarm call at the residents unit the operator should press the butt...

Страница 22: ... mode see above the alarm will regenerate after a predetermined time period Multiple Alarm Calls When several alarm calls are active at the same time the C200 will hold these in an internal Queue up to 4 calls in the order of priority then origination The Master unit will indicate the presence of more than one call by flashing both the flat number and the reassurance lamp red LED The operator may ...

Страница 23: ...r station without first visiting the flat and resetting the smoke detector Cancelling a Fire alarm for the Master station will however temporarily place the room unit into sleep mode the alarm call that will then re generate after a pre programmed time period 0 20 minutes Call For Assistance This facility is provided specifically for Nursing homes to enable staff to make an urgent alarm call for a...

Страница 24: ...18 September 2003 PD001 Iss 2 21 Diagram 4 Handling a Typical Alarm ...

Страница 25: ...e operator may establish communication from a Master unit with any M200 room unit even though it has not made an alarm call The operator must type the flat number up to 4 digits followed by the button e g To connect to flat 1759 Display Type 1759 1759 Display momentarily Press Display SPEECH LO 1759 ...

Страница 26: ... Flat Number If there is only one M200 unit on the system with the same number e g 11A 12A 13A The operator must type the numeric part of the flat number followed by the button e g To connect to flat 12A Display Type 12 12 Display momentarily Press Display SPEECH LO 12A ...

Страница 27: ...ne M200 units on the system with the same number e g 12 and 12A the operator must use the sbutton to select the correct M200 then press to connect to that unit e g To connect to flat 12B on a system that includes flats 12 12A 12B and 12C Display Type 12 12 Display momentarily Press Display SCROLL OR 12 ...

Страница 28: ...18 September 2003 PD001 Iss 2 25 Display Press s SCROLL OR 12A Display Press s SCROLL OR 12B Display Press SPEECH LO 12B Note To dial M200 unit with no number e g HALL dial 0 ...

Страница 29: ...oom unit both the Master unit and the unit being called will sound a brief tone This annunciation tone can be disabled by programming refer to the installation manual Privacy Operation During an operator connected call the following display message may be seen PRIVATE 12A This indicates that the unit being called has the privacy function activated The operator may talk but cannot hear until the re...

Страница 30: ...pts to call a non existent flat number one of the following messages will appear Flat number not recognised by the system UNAVAILABLE Flat number not available Room unit may be UNAVAILABLE 12A disconnected This message may be cancelled with the or will time out automatically ...

Страница 31: ...appear when returning the program slide switch to normal N and after system test refer to the installation manual If the message appears under any other circumstances it is an indication of power supply problems or other system faults call an engineer Fault Codes The M200 room unit constantly monitors the system and displays any permanent faults which would prevent normal operation e g Call an eng...

Страница 32: ...18 September 2003 PD001 Iss 2 29 C Products comply with EMC directive 89 336 EEC Standards Emissions Generic BSEN50081 1 Immunity Generic BSEN50082 1 IEC801 2 IEC801 6 ...

Страница 33: ...l up a Room Unit How to 22 Ceiling Pull Switch Alarm message 15 Descriptoin 4 Generating alarm 8 Central Control Display message 12 Display Message 10 22 24 ALARM 15 ALARM AUX 15 ALARM CANCEL 18 ALARM REM 15 ALL CALL ACTIVE 12 CENTRAL ACTIVE 12 ENTER CODE 10 FAULT 28 FIRE ALARM 16 HELP AT 16 M200 V1 0 28 MASTER 11 22 25 MASTER AT 12 NO CALLS 11 15 PRIVATE 7 PRIVATE NNNN 26 SPEECH HI 17 SPEECH LO 1...

Страница 34: ... Descriptoin 3 Diagram 1 Master Mode Activating 9 Descriptoin 9 Volume 17 Maximum Number of room units 3 Unit sounding alarm tones 9 Microphone Grill Location of 1 Monitor Mode Activating 9 Becoming a master 12 Descriptoin 9 Pear Drop Alarm message 15 Descriptoin 4 Dummy plug 4 Generating alarm 8 Removal 19 Power Supply Descriptoin 6 Presence Lamp Descriptoin 4 Operation 9 Privacy Button Location ...

Страница 35: ...alarm 8 Speaker Grill Location of 1 Speech Automatic cancelation 19 Cancellation 18 Start Up Display message 28 UnMastering Operation 13 UnMonitoring Operation 13 Urgent Help Alarm message 16 Cancellation 20 Descriptoin 20 Volume Adjusment 17 Initial level 17 ...