Action and Event Tables
91
Parameters
Action routines typically have parameters associated with them. A parameter may be a phone
number, a pager number, or other information used by the Action Routine.
Comments
The comment may give more information about the alarm. With some Action Routines, when the
ASG Guard/ASG Guard Plus processes an alarm, the comment is sent along with it.
8.4.1 Alarm Matching Criteria
When the ASG Guard/ASG Guard Plus receives an alarm, it follows a specific procedure when it
searches the Action Table for a match to an alarm (event). Three passes are made.
1.
In the first pass, the ASG Guard/ASG Guard Plus attempts to match the alarm from the first
character to the first space. That is, if it received an alarm ERR000 Reset, it would try to find
ERR000 in the Action Table and then take whatever action is specified.
2.
If the first search fails to turn up a match, it searches for a record describing a range of
alarms that includes the alarm it received. For example, if it received an alarm ERR004, it
might match this to ERR000 - 005, as it appears in the Action Table. Such ranges can be
entered into the Action Table to cover a multiple of alarm types.
3.
Finally, if there is no match using the first two criteria, it searches for a match to the
mnemonic up to the first digit. That is, it drops the digits and just tries to match the mnemonic
by itself. For example, if it received the alarm ERR006, but only ERR000, ERR010 - 020,
and ERR appear in the Action Table, it matches the ERR in ERR006 to ERR in the Action
Table.
In summary, there is a three pass lookup on Action Table:
•
Pass 1 - Exact Match (up to first space)
•
Pass 2 - Range Match
•
Pass 3 - Exact Match (up to first non-alpha)
Following are some examples of the alarm matching procedure.
Sample Action Table:
Alarm
Action Routine
Parameters
Comments
1.) ERR005
PHONHOME
2.) ERR000-030
PHONHOME
2
3.) ERR
PAGE
4.) .AUTHFAIL PAGE
5.) .AUTHFAIL.1
PAGE
Event:
ERR000
matches (2)
ERR005
matches (1)
ERR040
matches (3)
.AUTHFAIL
matches (4)
.AUTHFAIL.1
matches (5)
Содержание Lucent Technologies Access Security Gateway Guard
Страница 12: ...x Page intentionally left blank ...
Страница 28: ...ASG Guard Overview 16 Page intentionally left blank ...
Страница 36: ...Physical Connections 24 Page intentionally left blank ...
Страница 60: ...Modem Port Setup 48 Page intentionally left blank ...
Страница 82: ...Modifying the User Database 70 Page intentionally left blank ...
Страница 106: ...Action and Event Tables 94 ACTION TABLE WORKSHEET Alarm Message or Internal Event Action Routine Routine Parameters ...
Страница 120: ...Action and Event Tables 108 Page intentionally left blank ...
Страница 158: ...User Connectivity 146 Page intentionally left blank ...
Страница 188: ...Log Functions 176 Page intentionally left blank ...
Страница 236: ...Troubleshooting 224 Page intentionally left blank ...
Страница 252: ...Internal Battery Replacement 240 Page intentionally left blank ...
Страница 258: ...Glossary of Command References 246 Page intentionally left blank ...